Using the Command Interface
76
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
Table 3-5
Error Coding, continued
DONE
Meaning
STATUS
ERROR
0
1
83A3
H
An AS-i slave with the new address already exists on the
AS-Interface.
0
1
83A4
H
The AS-i slave address cannot be deleted.
0
1
83A5
H
The AS-i slave address cannot be set.
0
1
83A6
H
The AS-i slave address cannot be stored permanently.
0
1
83A7
H
Error reading the extended ID1 code.
0
1
83A8
H
The target address is not plausible (for example a B slave
address was used for a standard slave).
0
1
83B1
H
A length error has occurred transferring a string according
to profile 7.4.
0
1
83B2
H
A protocol error has occurred transferring a string
according to profile 7.4.
0
1
83F8
H
The job number or the job parameter is unknown.
0
1
83F9
H
The AS-i master has detected an EEPROM error.
0
1
8F22
H
Area length area reading a parameter
8F23
H
Area length error writing a parameter
This error code indicates that a parameter is entirely or
partly outside the address area or that the length of a bit
array of an ANY parameter cannot be divided by 8.
0
1
8F24
H
Area error reading a parameter
8F25
H
Area error writing a parameter
This error codes indicates that a parameter is located in an
area that is illegal for a system function.
0
1
8F28
H
Alignment error reading a parameter
8F29
H
Alignment error writing a parameter
This error code indicates that the reference to a parameter
is a bit address other than 0.
0
1
8F30
H
The parameter is in the write-protected global DB
8F31
H
The parameter is in the write-protected instance DB
This error code indicates that a parameter is located in a
write-protected data block.
0
1
8F32
H
The DB number in the parameter is too high
0
1
8F3A
H
The parameter contains the number of a DB that is not
loaded
0
1
8F42
H
An access error has occurred while the system attempted
to read out a parameter from the peripheral area of the
inputs.
0
1
8F43
H
An access error occurred while the system was attempting
to write a parameter to the peripheral area of the outputs
Содержание DP/AS-Interface Link 20E
Страница 6: ...Preface 6 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 10: ...Contents 10 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 124: ...Using the Command Interface 124 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 132: ...Slave Diagnostics 132 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 138: ...Dealing with Problems Error Displays 138 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 150: ...Notes on the CE Mark 150 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...