Using the Command Interface
96
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
3.3.15
Get_AS-i_Slave_Status
Purpose
With this call, the status register of the addressed AS-i slave can be read out.
Depending on the type of AS-i slave, the flags of the status register have the
following meaning:
Status
Bit
AS-i slave complying with standard 2.0
AS-i slave complying with standard
2.1
S 0
Address volatile
Address/ID code volatile
This flag is set when
S
the internal slave routine for permanent storage of the AS-i slave address is
active. This can take up to 15 ms and must not be interrupted by a further
addressing call.
S
the AS-i internal slave address comparison recognizes that the stored
address is not the same as the entry in the address register.
S 1
Parity error detected
This flag is set when the AS-i slave has
recognized a parity error in a received
frame since the last “read and delete
status” job.
I/O error detected
An AS-i slave can set this flag
when it has detected and error (for
example wire break) in the attached
I/Os.
S 2
End bit error detected
This flag is set when the AS-i slave has
recognized an end bit error in a frame
since the last “read and delete status” job.
reserved
S 3
Read error in non-volatile memory
This bit is set when the AS-i slave has detected a read error when reading the
non-volatile memory.
Structure of the Job Data in the Send Buffer
Byte
Meaning
0
Command number: 0F
H
1
Slave address
Structure of the Response Data in the Receive Buffer
Byte
Meaning
Bit 7
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
S 3
S 2
S 1
S 0
Содержание DP/AS-Interface Link 20E
Страница 6: ...Preface 6 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 10: ...Contents 10 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 124: ...Using the Command Interface 124 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 132: ...Slave Diagnostics 132 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 138: ...Dealing with Problems Error Displays 138 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 150: ...Notes on the CE Mark 150 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...