Using the Command Interface
75
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
Table 3-5
Error Coding
DONE
ERROR
STATUS
Meaning
1
0
0000
H
Job completed without error
0
1
8090
H
Address in LADDR invalid
0
1
8092
H
A type other than BYTE is specified in the ANY reference.
0
1
8093
H
This SFC is not permitted for the module selected with
LADDR and IOID. (S7-300 modules are permitted for
S7-300, S7-400 modules for S7-400, S7-DP modules for
S7-300 and S7-400.)
0
1
80A0
H
Negative acknowledgment when reading from AS-i master.
0
1
80A1
H
Negative acknowledgment when writing to AS-i master
0
1
80A2
H
DP protocol error at Layer 2
0
1
80A3
H
DP protocol error involving user interface/user
0
1
80A4
H
Communication problems on K bus
0
1
80B0
H
AS-i master does not recognize the data record
0
1
80B1
H
Specified data record length incorrect
0
1
80B2
H
The configured slot is not in use.
0
1
80B3
H
Actual module type does not match the expected module
type in SDB1
0
1
80C0
H
Data record cannot be read
0
1
80C1
H
The specified data record is currently being processed
0
1
80C2
H
There is a job pileup
0
1
80C3
H
Resource (memory) in use
0
1
80C4
H
Communication error
0
1
80C5
H
Distributed I/Os not available
0
1
80C6
H
Data record transfer aborted due to priority class abort
(warm restart or background) of the distributed I/Os.
0
0
8181
H
Job active (no error)
0
1
8182
H
ID following warm restart (STARTUP=TRUE)
0
1
8184
H
Data type of the RECV formal parameter illegal
0
1
8381
H
The AS-i slave address is incorrect
0
1
8382
H
The AS-i slave is not activated (not in LAS).
0
1
8383
H
Error on the AS-Interface
0
1
8384
H
Command not permitted in the current status of the AS-i
master.
0
1
8385
H
An AS-i slave with address 0 exists.
8386
H
The AS-i slave has illegal configuration data (I/O or ID
codes).
0
1
83A1
H
The addressed AS-i slave was not found on the
AS-Interface.
0
1
83A2
H
An AS-i slave with address 0 exists.
Содержание DP/AS-Interface Link 20E
Страница 6: ...Preface 6 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 10: ...Contents 10 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 124: ...Using the Command Interface 124 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...