Using the Command Interface
99
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
Flag 1
Flag 2
Bit Number
Meaning
Bit Number
Meaning
0
OFFLINE_READY
0
OFFLINE
1
APF
1
INTERNAL
2
NORMAL_MODE
2
EEPROM_OK
3
CONFIG_MODE
3
AUTO_ADDR_ENABLE
4
AUTO_ADDR_AVAIL
4
PERIPHERY_FAULT
5
AUTO_ADDR_ASSI_GN
5
reserved
6
LDS_0
6
reserved
7
CONFIG_OK
7
MPO startup
Meaning of the Flags
Flag
Meaning
OFFLINE_READY
The flag is set when the offline phase is active.
APF
This flag is set when the voltage on the AS-i cable is too low.
NORMAL_MODE
This flag is set when the DP/AS-i Link 20E is in the normal mode.
(The flag is set when the CP is in the normal mode.)
CONFIG_MODE
The flag is set in the configuration mode and reset in the protected mode.
AUTO_ADDR_AVAIL
This flag is set when the automatic address programming can be executed
(in other words, exactly one AS-i slave is currently out of operation).
AUTO_ADDR_ASSIGN
This flag is set when the automatic address programming is possible (in
other words, AUTO_ADDR_ENABLE = 1 and there is no “incorrect” slave
connected to the AS-i Interface).
LDS_0
This flag is set when an AS-i slave exists with address 0.
CONFIG_OK
This flag is set when the desired (configured) and actual configuration
match.
OFFLINE
This flag is set when the mode is to changed to OFFLINE or this mode has
already been adopted.
EEPROM_OK
This flag is set when the test of the internal EEPROM did not detect any
errors.
AUTO_ADDR_ENABLE
This flag indicates whether the automatic address programming is enabled
(BIT = 1) or disabled (BIT = 0) by the user.
INTERNAL
This flag is always set.
PERIPHERY_FAULT
This flag is set when at least one AS-i slave is signaling a peripheral fault.
MPO startup
The “master_power_on_startup” flag is set after the power supply of the
AS-i slave master has been turned on. If the master is later
changed to OFFLINE, the bit is reset.
Содержание DP/AS-Interface Link 20E
Страница 6: ...Preface 6 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 10: ...Contents 10 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 124: ...Using the Command Interface 124 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 132: ...Slave Diagnostics 132 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 138: ...Dealing with Problems Error Displays 138 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 150: ...Notes on the CE Mark 150 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...