Slave Diagnostics
130
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
Byte
Meaning
Value
11
04H
Fixed value
12
00H
Fixed value
Bytes 13 to 23 of the device-related diagnostic information contain error bits for
errors on the AS-Interface. A delta list (bytes 20.23) contains all the AS-i slaves
that deviate from the configuration, in other words missing, incorrect or existing but
not configured AS-i slaves.
Byte
Bit
Value/meaning
13
0
1: Group error bit
1
1: Internal error (for example EEPROM defective).
2
1: External error (for example slave failed or APF).
3
1: At least one slave differs from the expected configuration.
4
1: Voltage on the AS-Interface too low (APF).
5 ..7
0
Byte
Value
Meaning
14
1C
H
Module class.
Byte
Bit
Value/meaning
15
0
1: At least one AS-i slave differs from the expected configuration.
1
0
2
0: Normal status
1: The DP/AS-i Link 20E module is offline.
3
1: Hardware error (internal watchdog)
4..7
0
Byte
Bit
Value/meaning
16
0,1
0
2
1: EEPROM defective
4..7
0
Содержание DP/AS-Interface Link 20E
Страница 6: ...Preface 6 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 10: ...Contents 10 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 124: ...Using the Command Interface 124 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 132: ...Slave Diagnostics 132 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 138: ...Dealing with Problems Error Displays 138 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 150: ...Notes on the CE Mark 150 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...