Slave Diagnostics
128
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
Byte
Remedy
Value/meaning
Bit
4
1: Function not supported, e.g. changing
the DP address of the DP/AS-i Link 20E
module by the DP master.
Check the configuration.
5
1: The DP master cannot interpret the
response from the DP/AS-i Link 20E
module correctly.
Check the PROFIBUS.
6
1: The DP/AS-i Link 20E detects an
incorrect parameter assignment frame
(e.g. incorrect length, incorrect ID number,
incorrect parameters).
Check the configuration.
7
1: The DP/AS-i Link 20E module was
assigned parameters by a different DP
master from the DP master that currently
has access to the DP/AS-i Link 20E
module.
This bit is always 1 if, for example, you
are accessing the DP/AS-i Link 20E
module with a PG or a different DP
master. The DP address of the parameter
assignment master is in the diagnostic
byte“Master PROFIBUS Address”.
Station Status 2
Byte
Bit
Value/meaning
1
0
1: The DP/AS-i Link 20E module must have parameters reassigned by the DP
master.
1
1: A static diagnostic message exists.
2
1 :This bit is always ‘1’ with the DP/AS-i Link 20E module.
3
1: The response monitoring of the DP/AS-i Link 20E module is activated.
4
1: The DP/AS-i Link 20E module has received the“FREEZE” control command.
5
1: The DP/AS-i Link 20E module has received the“SYNC” control command.
6
0: This bit is always set to ‘0’.
7
1: The DP/AS-i Link 20E module is deactivated, in other words it is not taking
part in the current processing.
Station Status 3
Byte
Value/meaning
2
Station status 3 is reserved and is irrelevant for diagnostics on the DP/AS-i Link 20E module.
Содержание DP/AS-Interface Link 20E
Страница 6: ...Preface 6 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 10: ...Contents 10 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 124: ...Using the Command Interface 124 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 132: ...Slave Diagnostics 132 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 138: ...Dealing with Problems Error Displays 138 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 150: ...Notes on the CE Mark 150 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...