Using the Command Interface
121
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
3.3.29
Read_AS-i_Slave_Parameter_String
Purpose
With this call, a parameter string complying with AS-i slave profile 7.4 can be read
from the AS-i slave with the AS-i slave address specified in the send buffer.
The AS-i master supplies up to 221 bytes of response data. The number of
parameter bytes actually sent by the AS-i slave is signaled by the AS-I master in
byte 0 of the receive buffer (number of parameter bytes).
If the AS-i slave sends a string longer than 220 bytes, the AS-i master aborts the
string transfer and terminates the job with an error. The received data are then not
made available to the user program.
As long as the string transfer is active, there is no user/analog data exchange with
the addressed AS-i slave.
Structure of the Job Data in the Send Buffer
Byte
Meaning
0
Command number 41
H
1
Slave address
Structure of the Response Data in the Receive Buffer
Byte
Meaning
0
Number of parameter bytes
1
String byte (1)
2
String byte (2)
...
.....
String byte (n-1)
...
String byte (n)
Maximum value for n=220
Содержание DP/AS-Interface Link 20E
Страница 6: ...Preface 6 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 10: ...Contents 10 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 124: ...Using the Command Interface 124 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 132: ...Slave Diagnostics 132 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 138: ...Dealing with Problems Error Displays 138 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 150: ...Notes on the CE Mark 150 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...