Using the Command Interface
89
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
3.3.8
Store_Actual_Configuration
Purpose of the Command
With this call, the (actual) configuration data (I/O configuration, ID code, extended
ID1 code and extended ID2 code) of all AS-i slaves are stored permanently in the
EEPROM as the (expected) configuration data. The list of activated AS-i slaves
(LAS) is adopted in the list of permanent AS-i slaves (LPS).
When this command is executed, the AS-i master changes to the offline phase and
then changes back to the normal mode (warm restart on the AS-i master).
The call is not executed in the protected mode.
Note
If you use CPUs from the SIMATIC S7 system as the PROFIBUS DP master, then
dependent on the configuration in STEP 7, these may send a complete AS-i slave
configuration to the DP/AS-i Link 20E during the DP startup. Use of the call
described here is then generally unnecessary.
Structure of the Job Data in the Send Buffer
Byte
Meaning
0
Command number: 07
H
Содержание DP/AS-Interface Link 20E
Страница 6: ...Preface 6 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 10: ...Contents 10 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 124: ...Using the Command Interface 124 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 132: ...Slave Diagnostics 132 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 138: ...Dealing with Problems Error Displays 138 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...
Страница 150: ...Notes on the CE Mark 150 DP AS Interface Link 20E Release 11 2002 C79000 G8976 C138 04 ...