Type
Version
Restrictions
MM8000
MK8000
MP4.10
- NK8225 supports logical connections to a max. of 4
hosts via proprietary CMSDL/IP protocol
*
, OR via
BACnet/IP protocol
- Only one host can be supported using the CEI79-5
protocol
*
- Dial-up via CEI protocol and network-wide-interactions
**
via BACnet are currently not compatible
- Up to four CS6 Guarto intrusion panels per NK8225 are
supported
- NK8000 requires static IP-addresses (i.e. DHCP is not
supported)
- Default UDP Port 47808 (hex BAC0) for BACnet con-
nectivity (configurable)
- BACnet Broadcast Management Device (BBMD) is sup-
ported in NK8225 (NK8225 can be installed on different
TCP/IP subnets)
- Max. 150 COV subscriptions per device object
- Max. 10,000 pairs of BACnet multi-state input and multi-
state output objects are supported (soft limit)
*
See section 3.3.11 for configuration details for these protocols.
**