Automation level configurations
47
Siemens Building Technologies
DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en
Fire & Security Products
06.2007
Further options
The following are available for all of the NK822x products:
DF8040 8-input module
on I
2
C bus
–
8 input (non supervised) module for acquiring digital contacts. A
max of 2 modules can be directly connected to NK822x. For more
connectivity (as well as for supervised inputs), it is necessary to use
a CF9003 CPU on one of the serial connections.
DF8020 8-output relays
module on I
2
C bus
–
8 output (non supervised) relay module for controlling digital con-
tacts. Only one module can be directly connected to NK822x. For
more connectivity, it is necessary to use a CF9003 CPU on one of
the serial connections.
DF8090 power supply
supervision module on I
2
C
bus
–
Optional module for supervising the NK822x power supply and
detecting power failures and battery low conditions. It is not needed
when NK822x is installed in a fire or intrusion control unit, whose
power supply is already supervised.
NE8001
–
Wall-mountable, metallic cabinet with DIN-rail, including power
supply unit.
Input: 100
–
240 Vac; Output: 12Vdc 4A.
NE8002
–
Wall-mountable, metallic cabinet with DIN-rail.
NZ8201
–
NK822x mounting kit for CS11
Card holders and cable set for installing NK822x in CS11 or CS440
NZ8202
–
NK822x mounting kit for CS6 Guarto
Mounting plate, card holders and cable set for installing NK822x in
CS6
NZ8203
–
NK822x mounting kit for SI410 Sintony
Mounting plate, card holders and cable set for installing NK822x in
SI410 Sintony (standard or Scandinavian housings)
Further options: Cable for connecting SI410 to NK822x must be or-
dered separately from the intrusion product range (80064100001
SAQ18 Cable link X25 SAQ18).
Modem
–
NK8021 analog modem
Analog modem for public switched telephone network (PSTN)