Automation level configurations
26
Building Technologies
DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en
Fire Safety & Security Products
06.2007
Subsystems that can be connected in this way
Supported by
Type
Name
MM8000
MP4.10
MK8000
MP4.10
MT8001
MP3.15
Fire panel
CS11 AlgoRex
X
X
X
Fire panel
CZ10
X
X
X
Intrusion panel
CS440
X
X
X
Intrusion panel
CS4
X
X
Intrusion panel
CZ12
X
X
Gas panel
CC60
X
X
X
Digital PLC unit
MF/MM7033
X
X
X
Syst
è
me de
T
é
l
é
commande et
T
é
l
é
signalisation
STT11
X
X
X
Network devices required
Type
Name
Version
Gateway for Cerloop
MK7022
‡
Gateway for CS11
CK1142
‡
Gateway for STT11
SK11
Additional components required for the various management station types
Type
Additional
components
Name
Version
Foreign station
OPC client head end
Any OPC DA2.0x
compliant client
OPC DA2.0x
OPC Server
MK8000
MP4.10
ISO1745 Driver
NS8010
MM8000
ISO1745 Driver
NS8010
MP4.10
MT8001
None
MP3.15
Limits and restrictions
Type
Version
Restrictions
MM8000
MK8000
MP4.10
With stand-alone/server stations, up to three serial
connections to ISO1745 driver (three MK7022).
More lines can be supported via FEP stations (max 8
lines per FEP).
MT8001
MP3.15
One serial connection only.
Note: Up to four data evaluation devices (MM8000 / MK8000 / MT8001 / MF7033)
may be connected to the Cerloop.
‡
See MM8000 MP4.10 Release Notes (STEP #A6V10062455)