Automation level configurations
42
Building Technologies
DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en
Fire Safety & Security Products
06.2007
Additional components required for the various management station types
Type
Additional
components
Name
Version
Foreign station
OPC client head end
Any OPC DA2.0x
compliant client
OPC DA2.0x
OPC Server
MK8000
MP4.10
Network Driver
NS8210
MM8000
Network Driver
NS8210
MP4.10
Modem
NK8021 (Analog);
Siemens M20 or
MC35i (GSM)
Limits and restrictions
Type
Version
Restrictions
MM8000
MK8000
MP4.10
- NK822x supports logical connections to a max. of 4
hosts (MM8000 and/or MK8000) via CMSDL/IP protocol
- Only one host can be supported using the CEI 79-5 en-
crypted protocol
- Up to 500 NK822x can be connected to an MM8000 /
MK8000, however please contact customer support for
configurations of over 100
- Upstream serial connectivity is limited to one host
- Up to four CS6 Guarto intrusion panels per NK8223 /
NK8225 are supported
- NK822x supports one modem, and up to 5 phone num-
bers
- GSM modems: SIM pin must be disabled
- NS8210 Network Driver supports up to 64 modems
- NK8000 requires static IP-addresses (i.e. DHCP is not
supported)
MT8001
MP3.15
LAN connections to the NK822x are not supported