Automation level configurations
34
Building Technologies
DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en
Fire Safety & Security Products
06.2007
3.3.7
BACnet/IP LAN configuration
Fig. 15
Direct LAN configuration for subsystems
System architecture
This configuration allows for the integration of DESIGO PX building automation con-
trollers.
Communication / connection
The subsystems are connected to the DMS via LAN.
Subsystems that can be connected in this way
Supported by
Type
Name
MM8000
MP4.10
MK8000
MP4.10
MT8001
MP3.15
Building
automation
DESIGO
PX
‡
X
Additional components required for the various management station types
Type
Additional
components
Name
Version
Foreign station
OPC client head end
Any OPC DA2.0x
compliant client
OPC DA2.0x
OPC Server
MK8000
MP4.10
BACnet Driver
NS8011
MM8000
BACnet Driver
NS8011
MP4.10
Limits and restrictions
Type
Version
Restrictions
MM8000
MP4.10
Displays events to indicate when conditions are
abnormal
–
no additional information regarding an
event is available on the management station.
Up to 50 DESIGO PX can be connected.
‡
MT8001
MP3.15
DESIGO PX not supported.
‡
See MM8000 MP4.10 Release Notes (STEP #A6V10062455) for PX models and quantity supported.