Chapter 4 - 7SR45 Data Communications Definitions
© 2018 Siemens Protection Devices Limited
Chapter 4 Page 9 of 20
4.3
Event Function (FUN) & Information (INF) Numbers
FUN
INF
Description
ASDU
COT
60
13
Command Received
1
SE
60
128
Cold Start
1
SE, GI
60
129
Warm Start
1
SE, GI
60
130
Re-Start
1
SE, GI
60
131
Expected Restart
1
SE, GI
60
132
Unexpected Restart
1
SE, GI
60
137
Clear Fault Records
1
SE
60
138
Clear Event Records
1
SE
60
145
CT Input
1
SE, GI
60
147
Aux Input
1
SE, GI
60
149
IRF
1
SE, GI
60
153
Battery Volts Low
1
GI
60
158
Battery Volts Critical
1
GI
60
170
General Alarm 1
1
SE, GI
60
171
General Alarm 2
1
SE, GI
60
172
General Alarm 3
*
1
SE, GI
60
173
General Alarm 4
*
1
SE, GI
60
4
Remote Mode
1
SE, GI
20
Ack, Nak
60
5
Service Mode
1
SE, GI
20
Ack, Nak
60
6
Local Mode
1
SE, GI
20
Ack, Nak
60
7
Local & Remote Mode
1
SE, GI
20
Ack, Nak
80
1
Binary Output 1
1
SE, GI
20
Ack, Nak
80
2
Binary Output 2
1
SE, GI
20
Ack, Nak
80
3
Binary Output 3
*
1
SE, GI
20
Ack, Nak
80
4
Binary Output 4
*
1
SE, GI
20
Ack, Nak
80
66
Trip Pulse Output
1
SE, GI
90
1
LED 1
1
GI
90
2
LED 2
1
GI
90
3
LED 3
1
GI
90
4
LED 4
1
GI
90
5
LED 5
1
GI
90
6
LED 6
1
GI
90
7
LED 7
1
GI
90
8
LED 8
1
GI
90
9
LED 9
1
GI
160
2
Reset FCB
5
SE
160
3
Reset CU
5
SE
160
4
Start/Restart
5
SE
160
5
Power On
1
SE, GI
160
19
LEDs reset (Reset Flag & Outputs)
1
SE
20
Ack, Nak
160
22
Settings changed
1
SE