Chapter 1 - 7SR45 Description of Operation
©2018 Siemens Protection Devices Limited Chapter 1 Page 38 of 48
Table 3-12
Binary Input
Parameters
Description
Default Value
Min
Max
Step Change
Inhibit 50-1
50-1 element block
-
-
1
-
Inhibit 50-2
50-2 element block
-
-
1
-
Inhibit 51-1
51-1 element block
-
-
1
-
Inhibit 50N-1
50N-1 element block
-
-
1
-
Inhibit 50N-2
50N-2 element block
-
-
1
-
Inhibit 51N-1
51N-1 element block
-
-
1
-
Inhibit 50G-1
50G-1 element block
-
-
1
-
Inhibit 50G-2
50G-2 element block
-
-
1
-
Inhibit 51G-1
51G-1 element block
-
-
1
-
Inhibit 50LC
50LC/SOTF element block
-
-
1
-
Select Group 1
#
Select Group 1
-
-
1
-
Select Group 2
#
Select Group 2
-
-
1
-
Rst LEDs & O/Ps
Reset LEDs and BOs
-
-
1
-
Trip Pulse O/P
Pulse output
-
-
1
-
Local mode
#
Local mode
-
-
1
-
Remote mode
#
Remote mode
-
-
1
-
Local or Remote mode
#
Local or Remote mode
-
-
1
-
Out Of Service mode
#
Out Of Service mode
-
-
1
-
General Alarm-1
Display General alarm-1 text -
-
1
-
General Alarm-2
Display General alarm-2 text -
-
1
-
General Alarm-3 *
Display General alarm-3 text -
-
1
-
General Alarm-4 *
Display General alarm-4 text -
-
1
-
NOTE:
*
For 7SR4501 variants, these parameters are not available.
#
For 7SR4501-xGA10-1AA0 variant, these parameters are not available.
Table 3-13
Binary Input Configuration
Parameters
Description
Default Value
Min
Max
Step Change
Inverted Inputs
Input Inversion
-
-
1
-
BI-n Pickup
Pickup delay
0.020
0 s
< 20 s
0.01
≥
20 s
< 100 s
0.1
≥
100 s
600 s
1
BI-n dropoff
Dropoff delay
0.000
0 s
< 20 s
0.01
≥
20 s
< 100 s
0.1
≥
100 s
600 s
1
Enabled in Local
Enabled in Local mode
1 (all BIs)
-
1
-
Enabled in Remote Enabled in Remote mode 1 (all BIs)
-
1
-
NOTE:
Depending on the number of binary inputs, the sleep mode current will increase if the binary input is connected
and energized in the sleep mode.
NOTE:
When any binary input is assigned to Trip Pulse Output and when the TEST/RESET key is pressed, a
“
FAULT/ MAINT PERSISTS
” pop up appears.