Chapter 4 - 7SR45 Data Communications Definitions
© 2018 Siemens Protection Devices Limited
Chapter 4 Page 10 of 20
160
23
Settings Group 1 Select
1
SE, GI
20
Ack, Nak
160
24
Settings Group 2 Select
1
SE, GI
20
Ack, Nak
160
27
Binary Input 1
1
SE, GI
160
28
Binary Input 2
1
SE, GI
160
29
Binary Input 3
*
1
SE, GI
160
30
Binary Input 4
*
1
SE, GI
160
64
Start/Pick-up L1
2
SE, GI
160
65
Start/Pick-up L2
2
SE, GI
160
66
Start/Pick-up L3
2
SE, GI
160
67
Start/Pick-up N
2
SE, GI
160
69
Trip L1
2
SE, GI
160
70
Trip L2
2
SE, GI
160
71
Trip L3
2
SE, GI
160
84
General Start/Pick Up
2
SE, GI
160
90
Trip I>
2
SE
160
91
Trip I>>
2
SE
160
92
Trip In>
2
SE
160
93
Trip In>>
2
SE
183
0
Data lost
1
SE
183
10
51-1
2
SE, GI
183
11
50-1
2
SE, GI
183
12
51N-1
2
SE, GI
183
13
50N-1
2
SE, GI
183
14
51G-1
2
SE, GI
183
15
50G-1
2
SE, GI
183
17
50-2
2
SE, GI
183
19
50N-2
2
SE, GI
183
21
50G-2
2
SE, GI
183
225
50 LC
2
SE, GI
183
239
In Fault Current
4
SE
183
240
Ia Fault Current
4
SE
183
241
Ib Fault Current
4
SE
183
242
Ic Fault Current
4
SE
183
243
Ig Fault Current
4
SE
255
0
Time Synchronisation
6
Time Synchronisation
255
0
GI Initiation
7
GI
255
0
End of GI
8
End of GI
NOTE:
* For 7SR4501 Dual Powered Relay variant, these parameters are not available.
NOTE:
For the list of events raised, refer to
Appendix 2
.