Chapter 3 - 7SR45 Performance Specification
©2018 Siemens Protection Devices Limited
Chapter 3 Page 8 of 14
Table 1-13
Electrical Tests
Type Test
Reference
Requirement
Insulation Resistance
IEC 60255-27
#
,
Edition 2.0
Insulation resistance >100 MOhm at
500 V DC
Test Duration: > 5 s
(Between any terminal and earth, independent
circuits)
^
Impulse Voltage
Withstand
IEC 60255-27
#
,
Edition 2.0
5 kV, 1.2/50 µs, 0.5 J
5 +ve, -ve pulses
(Between all terminals and case earth and any
two independent circuits)
^
AC Dielectric Voltage
IEC 60255-27
#
,
Edition 2.0
•
All case terminals connected together
2.0 kV AC RMS, 1 min
(Between terminals of independent circuits)
^
•
1.0 kV AC RMS, 1 min
(across normally open contacts)
Slow Damped Oscillatory
Wave
$
IEC 60255-26
•
Common-mode test voltage:
Test voltage: 2.5 kV peak voltage
•
Differential mode:
Test voltage: 1.0 kV peak voltage
•
Test duration: 2 s
•
Source impedance: 200
Ω
•
Voltage oscillation frequency: 1 MHz
•
Repetition frequency: 400 Hz
Electrostatic Discharge
IEC 60255-26
•
8 kV air discharge
•
6 kV contact discharge
Electrical Fast Transient
or Burst
$
IEC 60255-26
Zone B
Test severity Amplitude:
±
2 kV
Repetition frequency: 5 kHz
Surge Immunity
*
$
IEC 60255-26
Test Level : Zone A
Line to Line : 0.5, 1, 2 kV
Line to Earth : 0.5, 1, 2, 4 kV
Front time/Time to half-value : 1.2/50
µ
s
Source Impedance : 2 Ohm
Radiated Immunity
IEC 60255-26
Test field strength, frequency band
80 MHz to 1.0 GHz and 1.4 GHz to 2.7 GHz
Field strength: 10 V/m (RMS)
Test using AM: 1 kHz/80 %
Conducted Radio
Frequency Interference
$
IEC 60255-26
150 kHz to 80 MHz
10 V (RMS), Dwell time: 0.5 s
Power Frequency
Magnetic Field
IEC 60255-26
30 A/m applied 1 min,
300 A/m applied for 3 s
Radiated Emissions
IEC 60255-26
30 MHz – 230 MHz, 40 dB µ V/m (quasi peak)
230 MHz – 1 GHz, 47 dB µ V/m (quasi peak)
Limits are measured at 10 m distance