Br3

USER’S GUIDE

PROGRAMMABLE 3-RELAY LOGIC MODULE

1   Description

75.5501.02  EN   20091102   (75.5500)   

 

 

 

 

 

 

 

Page 1 of 15

The Br3 is a programmable 3 relay logic module that may be used for 

multiple applications, including simple timing, door mounted sensor 

inhibiting and advanced relay sequencing. The Br3 contains 12 

different programmable functions which allow the technician to carry 

one and only one module.

In addition to the ability to provide up to 3 Amps through the first 

two relays and 1 Amp through the third relay used in ‘‘DRY’’ mode, 

the Br3 provides the ability to select a ‘WET’ voltage output of 

up to 1 Amp on Relay 1 to power electric strikes and magnetic 

locks without the need for an external power supply. This feature 

can greatly simplify the installation (as long as the power supply 

powering the Br3 is rated for 1 Amp).

The ‘WET’ output can also be set using jumpers to output DC if the Br3 is supplied with AC, otherwise it will just pass the AC voltage that is 

supplied. Similarly if powered by DC, the ‘WET’ output will only output DC.

The module provides removable screw terminal connectors which help to reduce extra wiring.

Another feature of the Br3 is that it also provides an easy 2-button digital programming with a user-friendly display, hold times being adjustable 

from 0 to 60 seconds, and delay times being adjustable from 0 to 60 seconds with ¼, ½ and ¾ also available to the applicable functions. 

Programming

Push 

Buttons

‘WET’ Output Selector

Inputs / Outputs

Br3 APPLICATIONS GUIDE

(Refer to the corresponding page number for a more detailed description and programming of each function.)

FUNCTION SUBJECT

DESCRIPTION

PAGE

1 0

(MC10)

Simple Timer

Provides an activation of Relay 1 triggered by Input  1. The function also provides an option for 

reverse-logic on the activation of Input 1.

4

1 1

(MC11)

Ratchet/Latching

Provides a ratcheting/latching of Relay 1 triggered by Input 1.  Each trigger of Input 1 will change the 

state of Relay 1.

4

2 1

(LE21)

Inhibitor w/Door 

Position Input

Provides an activation of Relay 1 with an inhibitor of activation of  Input 1 until Input 2, Input 3 or 

‘WET’ Input is triggered, which all activate Relay 1. Additionally Input 4 provides a door position switch 

input for which closing it will re-inhibit Input 1.

5

2 2

(LE22)

2 Relay Sequence 

Inhibitor w/Door 

Position Input

Provides a sequence for Relay 1 and/or Relay 2 with an inhibitor of activation of Input 1 until Input 

2, Input 3 or ‘WET’ Input is triggered, which all activate the sequence.  Additionally Input 4 provides 

a door position switch input for which closing it will re-inhibit Input 1.  Simply put this function is a 

combination between a LE21 and MC25.

6

2 5

(MC25)

2 Relay Sequence Provides a sequence for Relay 1 and/or Relay 2 triggered by Input 1 or ‘WET’ Input. 

7

2 8

(MC28)

2 Relay Sequence 

w/Door Position 

Input

Provides a sequence for Relay 1 and/or Relay 2 triggered by Input 1 or ‘WET’ Input.  Additionally Input 

2 provides a door position switch input which allows the delay to run when Input 2 is opened, but not 

run when closed.  Simply put, this function is an MC25 with a normally opened door position switch 

input to determine if the delay should run.

8

2 9

(MC29)

Relay 1 

Deactivation 

Timer

Provides a sequence for Relay 1 and/or Relay 2 triggered by Input 1 or ‘WET’ Input.  Additionally Input 

2 provides a door position switch input which allows Relay 1 to deactivate once Input 2 is opened after 

the sequence has run.  Input 2 also allows the delay to run when Input 2 is opened, but not run when 

closed, as in the MC28.  Input 3 provides an input to disable the sequence whose input logic is also 

selectable.  Simply put Relay 1 will be active the entire time until the normally opened door position 

switch signifies that the door has come closed again.

9

3 5

(MC35)

3 Relay Sequence Provides a sequence for Relay 1 and/or Relay 2 and/or Relay 3 triggered by Input 1 or ‘WET’ Input.  

Simply put this function is a MC25 with three relays instead of two.

10

5 0

(MC50)

Interlock Timer 

w/Door Position 

Inputs

Provides an interlock of Relay 1 and Relay 2 triggered by Inputs 1 and 2, with door position switch 

inputs on Input 3 for Input 1and Input 4 for Input 2.  Only one relay will be allowed to operate at a 

time thus making the two relays interlocked or mutually exclusive.  In order to activate a relay, its 

corresponding position switch input must be closed.

11

5 5

(MC55)

Interlock Ratchet 

w/Door Position 

Inputs

Provides an interlock ratchet of Relay 1 and Relay 2 triggered by Inputs 1 and 2, with door position 

switch inputs on Input 3 for Input 1 and Input 4 for Input 2. Only one Relay will be allowed to operate 

at a time thus making the two relays interlocked or mutually exclusive.  In order to activate a relay, its 

corresponding position switch input must be closed. Each trigger of an input will change the state of its 

respective relay. 

12

6 5

(MC65)

2-Way, 2 Relay 

Sequence

Provides a two-way sequencer to sequence Relay 1 and/or Relay 2 triggered by Input 1.  Similarly, it 

also provides a sequence in the opposite direction to sequence Relay 2 and/or Relay 1 triggered by 

Input 2.  Inputs 3 and 4 also trigger Relays 1 and 2 individually.  

13

7 5

(MC75)

2 Relay Sequence Provides a sequence for Relay 1 and/or Relay 2 triggered by Input 1 or ‘WET’ Input.  

14

Содержание Br3

Страница 1: ...n switch input for which closing it will re inhibit Input 1 Simply put this function is a combination between a LE21 and MC25 6 2 5 MC25 2 Relay Sequence Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input 7 2 8 MC28 2 Relay Sequence w Door Position Input Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input Additionally Input 2 provides a do...

Страница 2: ...IPTION SPECIFICATION Supply Voltage 12 to 24 VAC VDC 10 Contact Rating DRY Relay 1 Relay 2 Relay 3 Contact Rating WET Relay 1 3 A at 24 VAC 3 A at 30 VDC 3 A at 24 VAC 3 A at 30 VDC 1 A at 24 VAC 1 A at 30 VDC 1 A Current Consumption 30 to 130 mA DRY Output Temperature Range 15 F 26 C to 150 F 65 C Dimensions 5 2 133mm W x 2 2 55mm D x 1 25mm H Input Specification Inputs 1 to 4 DRY Contact WET Inp...

Страница 3: ...long as no relays are active the display will show the function selected otherwise it will show those relays Once the values are changed they are only saved after the display goes inactive again 5 seconds NOTE Remember that the INCR push button always increments the value of the parameter that you are looking at and the PARAM push button toggles through the available parameters NOTE To change only...

Страница 4: ...system is in compliance with all applicable standards i e ANSI A156 10 A156 19 75 5501 02 EN 20091102 75 5500 Page 4 of 15 6A Function 10 Timer Module MC10 GND IN 1 GND IN 2 GND IN 3 GND IN 4 1 2 3 4 WET WET WET NC NO COM NC NO COM 12 24V AC DC RELAYS 1 2 POWER RELAY 1 INCR PARAM SETUP DC AC DRY WET INPUTS 1 0 NC NO COM 3 Br3 CAUTION RELAY 1 WET OUTPUT OPTION IS ACTIVE FOR ALL FUNCTIONS 12 to 24 V...

Страница 5: ...le parameter for the LE21 function is shown in the chart Set it as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of an activation input 4 Once programming is complete test the Br3 Attemp...

Страница 6: ...M button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the LE22 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time wil...

Страница 7: ...ding to the steps outlined in Section 5 Selecting the Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC25 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VA...

Страница 8: ...ers Press the INCR button to increment the parameter s value Parameters for the MC28 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release o...

Страница 9: ...METER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 2 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the delay between Relay 1 and Relay 2 expires D1 Delay between Relay 1 and Relay 2 00 _1 1 4 _2 1 2 _3 3 4 01 through 60 seconds The delay tim...

Страница 10: ... application it will still function as Input 1 does if used MC35 SETUP 1 Wire the Br3 accordingly 2 Select the MC35 as the function according to the steps outlined in Section 5 Selecting the Function Press and hold both push buttons INCR PARAM for three 3 seconds to activate the display Press the INCR button to toggle through each function and select 35 3 Set the MC35 parameters according to the s...

Страница 11: ...ay to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the release of Input 2 4 Once programming is complete test the Br3 Wait until both doors a...

Страница 12: ...set for the MC55 as the state of Relay 1 and Relay 2 are not based on time so just wait for the display to become inactive to save the configuration 4 Once programming is complete test the Br3 Wait until both doors are closed then trigger Relay 1 via Input 1 Ensure that Relay 1 changes state and that is maintained The display will show R1 when Relay 1 is energized Test the interlock by attempting ...

Страница 13: ...n to increment the parameter s value Parameters for the MC65 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 for inbound or...

Страница 14: ...e Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC75 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 ...

Страница 15: ...programmed 3 Jumper an active Input and ensure that the fault is not within the wiring If module works when jumped trace wiring from Inputs relays 4 Replace module Module reacts to input but has no output 1 Wrong outputs are connected 2 Incorrect wiring 3 Incorrect jumper settings 4 Faulty module 1 Check to ensure that the proper outputs are connected per the function selected 2 Trace all wiring t...

Отзывы: