background image

9   Company Contact

Do not leave problems unresolved. If a satisfactory solution cannot be achieved after troubleshooting a problem, please 

call BEA, Inc.  If you must wait for the following workday to call BEA, leave the door inoperable until satisfactory repairs 

can be made.   Never sacrifice the safe operation of the automatic door or gate for an incomplete solution.

The following numbers can be called 24 hours a day, 7 days a week.  For more information, visit www.beasensors.com.

East:

Canada and Texas:

1-866-249-7937

1-866-836-1863

Central:

West:

1-800-407-4545

1-888-419-2564

PROBLEM

PROBABLE CAUSE

CORRECTIVE ACTION

Module will NOT react to any input. 1.  Incorrect Br3 power

2.  Module not programmed

3.  Incorrect wiring

4.  Faulty module

1.  Check the Br3’s power. It should be 12 to 24 volts AC or DC +/- 10%.      

     Ensure that input power is applied at the correct terminals.

2.  Ensure a function has been programmed. If ‘

00

‘ is showing in the 

display, the Br3 will need to be programmed.

3.  Jumper an active Input and ensure that the fault is not within the wiring.

     If module works when jumped, trace wiring from Inputs / relays.

4.  Replace module.

Module reacts to input but has no 

output.

1.  Wrong outputs are

     connected

2.  Incorrect wiring

3.  Incorrect jumper settings

4.  Faulty module

1.  Check to ensure that the proper outputs are connected per the function

     selected.

2.  Trace all wiring to ensure correct termination points.

3.  Check that the jumpers are configured correctly for the application.

4.  Replace module

8   Troubleshooting

1.   Document all work. For future reference, be sure to record the Br3 Serial Number on your Work Order.
2.   Educate the Owner / Manager as to the proper operation of the door and sensor system, and what to do to ensure safe use of the door in the 

event of discovering a malfunction. Show the Owner / Manager how to perform a daily safety check of the system. You may also wish to provide 

the owner/Manager a copy of an owners manual provided by AAADM for the type of door selected.

3.   Be sure to obtain signatures on your work order for all work accomplished.

7   Documentation

Page 15 of 15 

 

 

 

 

 

 

 

 

 

75.5501.02  EN   20091102   (75.5500)

Содержание Br3

Страница 1: ...n switch input for which closing it will re inhibit Input 1 Simply put this function is a combination between a LE21 and MC25 6 2 5 MC25 2 Relay Sequence Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input 7 2 8 MC28 2 Relay Sequence w Door Position Input Provides a sequence for Relay 1 and or Relay 2 triggered by Input 1 or WET Input Additionally Input 2 provides a do...

Страница 2: ...IPTION SPECIFICATION Supply Voltage 12 to 24 VAC VDC 10 Contact Rating DRY Relay 1 Relay 2 Relay 3 Contact Rating WET Relay 1 3 A at 24 VAC 3 A at 30 VDC 3 A at 24 VAC 3 A at 30 VDC 1 A at 24 VAC 1 A at 30 VDC 1 A Current Consumption 30 to 130 mA DRY Output Temperature Range 15 F 26 C to 150 F 65 C Dimensions 5 2 133mm W x 2 2 55mm D x 1 25mm H Input Specification Inputs 1 to 4 DRY Contact WET Inp...

Страница 3: ...long as no relays are active the display will show the function selected otherwise it will show those relays Once the values are changed they are only saved after the display goes inactive again 5 seconds NOTE Remember that the INCR push button always increments the value of the parameter that you are looking at and the PARAM push button toggles through the available parameters NOTE To change only...

Страница 4: ...system is in compliance with all applicable standards i e ANSI A156 10 A156 19 75 5501 02 EN 20091102 75 5500 Page 4 of 15 6A Function 10 Timer Module MC10 GND IN 1 GND IN 2 GND IN 3 GND IN 4 1 2 3 4 WET WET WET NC NO COM NC NO COM 12 24V AC DC RELAYS 1 2 POWER RELAY 1 INCR PARAM SETUP DC AC DRY WET INPUTS 1 0 NC NO COM 3 Br3 CAUTION RELAY 1 WET OUTPUT OPTION IS ACTIVE FOR ALL FUNCTIONS 12 to 24 V...

Страница 5: ...le parameter for the LE21 function is shown in the chart Set it as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of an activation input 4 Once programming is complete test the Br3 Attemp...

Страница 6: ...M button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the LE22 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time wil...

Страница 7: ...ding to the steps outlined in Section 5 Selecting the Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC25 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VA...

Страница 8: ...ers Press the INCR button to increment the parameter s value Parameters for the MC28 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release o...

Страница 9: ...METER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 2 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the delay between Relay 1 and Relay 2 expires D1 Delay between Relay 1 and Relay 2 00 _1 1 4 _2 1 2 _3 3 4 01 through 60 seconds The delay tim...

Страница 10: ... application it will still function as Input 1 does if used MC35 SETUP 1 Wire the Br3 accordingly 2 Select the MC35 as the function according to the steps outlined in Section 5 Selecting the Function Press and hold both push buttons INCR PARAM for three 3 seconds to activate the display Press the INCR button to toggle through each function and select 35 3 Set the MC35 parameters according to the s...

Страница 11: ...ay to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 H2 Relay 2 hold time 00 through 60 Relay 2 hold time will not begin counting down until the release of Input 2 4 Once programming is complete test the Br3 Wait until both doors a...

Страница 12: ...set for the MC55 as the state of Relay 1 and Relay 2 are not based on time so just wait for the display to become inactive to save the configuration 4 Once programming is complete test the Br3 Wait until both doors are closed then trigger Relay 1 via Input 1 Ensure that Relay 1 changes state and that is maintained The display will show R1 when Relay 1 is energized Test the interlock by attempting ...

Страница 13: ...n to increment the parameter s value Parameters for the MC65 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 Relay 1 hold time will not begin counting down until the release of Input 1 for inbound or...

Страница 14: ...e Function Press PARAM button to cycle through and set the parameters Press the INCR button to increment the parameter s value Parameters for the MC75 function are shown in the chart Set the parameters as needed for the application and wait for the display to become inactive to save the configuration PARAMETER PARAM Button DESCRIPTION POSSIBLE VALUES INCR Button H1 Relay 1 hold time 00 through 60 ...

Страница 15: ...programmed 3 Jumper an active Input and ensure that the fault is not within the wiring If module works when jumped trace wiring from Inputs relays 4 Replace module Module reacts to input but has no output 1 Wrong outputs are connected 2 Incorrect wiring 3 Incorrect jumper settings 4 Faulty module 1 Check to ensure that the proper outputs are connected per the function selected 2 Trace all wiring t...

Отзывы: