Chapter 1 - 7SR45 Description of Operation
©2018 Siemens Protection Devices Limited Chapter 1 Page 40 of 48
Table 3-14
Binary Output
Parameters
Description
Default Value
Min
Max Step
Change
50-1
50-1 element operate
-
-
1
-
50-2
50-2 element operate
-
-
1
-
51-1
51-1 element operate
-
-
1
-
50N-1
50N-1 element operate
-
-
1
-
50N-2
50N-2 element operate
-
-
1
-
51N-1
51N-1 element operate
-
-
1
-
50G-1
50G-1 element operate
-
-
1
-
50G-2
50G-2 element operate
-
-
1
-
51G-1
51G-1 element operate
-
-
1
-
50LC
50LC/SOTF element operate
-
-
1
-
Active Grp 1
#
Active Group 1
-
-
1
-
Active Grp 2
#
Active Group 2
-
-
1
-
General Pickup
Pickup detected
-
-
1
-
Prot'n Healthy
Protection Healthy
-
-
1
-
Low Battery
Battery Volts low indication
-
-
1
-
IRF
Internal Relay Failure
1 (BO1), - (Others)
-
1
-
Local mode
#
Local mode
-
-
1
-
Remote mode
#
Remote mode
-
-
1
-
Out of Service mode
#
Out of Service mode
-
-
1
-
BI1 Operated
BI-1 operated
-
-
1
-
BI2 Operated
BI-2 operated
-
-
1
-
BI3 Operated *
BI-3 operated
-
-
1
-
BI4 Operated *
BI-4 operated
-
-
1
-
NOTE:
*
For all 7SR4501 variants, these parameters are not available.
NOTE:
#
For 7SR4501-xGA10-1AA0 variant, these parameters are not available.
NOTE:
If a binary output is assigned to IRF, do not use the same binary output for any other functions.
3.13 Binary Output Operations
The relay reset can be performed from the
Relay Identifier Screen > TEST/RESET
►
key.
If the fault current persists and if the user presses
TEST/RESET
►
key, the pop-up message appears,
“
FAULT PERSISTS
”
.
Based on the availability of power source, the flag can be reset by using any one of the following conditions:
3.13.1 BO Trip/Reset on Battery/USB
In this mode, the relay uses the power from battery/USB to operate/reset the binary output and takes
approximately 4s to perform the action.
If the consecutive commands are provided within 4 seconds, the relay performs delayed operations and displays
a pop-up message appears on the HMI “
INSUFFICIENT ENERGY”.
3.13.2 BO Trip/Reset on CT Input or Auxiliary Voltage
In this mode, the relay can operate/reset the binary outputs instantaneously.