Chapter 2 - 7SR45 Settings & Instrument Guide
© 2018 Siemens Protection Devices Limited Chapter 2 Page 8 of 9
2.1.3
Configuring Relay Serial Data Communication
This section is applicable for configuring the 7SR45 Argus Dual Powered Relay.
Using the keys on the relay fascia scroll down the settings menus into the ‘communications’ menu and if
necessary change the settings for the communication port you are using on the relay. Reydisp software uses
IEC60870-5-103 protocol to communicate.
When connecting the relay to a PC using the front USB port, the Reydisp setting software will automatically detect
the relay without making any setting changes in the relay first as long as the USB is selected to IEC60870-5-103.
Table 2-1
COM1-RS485 Port and COM2-USB Port
Description
Range
Default
COM1-RS485 Protocol
Selects protocol to use for COM1-RS485
OFF, IEC60870-5-103, MODBUS-RTU
MODBUS-RTU
COM1-RS485 Station Address
Sets the station address for COM1-RS485
0 - 254 for IEC60870-5-103
1 - 247 for Modbus RTU
1
COM1-RS485 Baud Rate
Sets the communications baud rate for COM1-RS485
1200, 2400, 4800, 9600, 19200, 38400,
57600
19200
COM1-RS485 Parity
Selects whether parity information is used
NONE, ODD, EVEN
NONE
COM1-RS485 Mode
Selects whether the port is Local or Remote.
Local, Remote, Local Or Remote
Local or Remote
COM2-USB Protocol
Selects protocol to use for COM2-USB
OFF, MODBUS-RTU, IEC60870-5-103
IEC60870-5-103
COM2-USB Station Address
Sets the station address for COM2-RS485
0, 1 ... 254
1
COM2-USB Mode
Selects whether the port is Local or Remote.
Local, Remote, Local Or Remote
Local or Remote