Chapter 3 - 7SR45 Performance Specification
© 2018 Siemens Protection Devices Limited
1.3 Environmental Performance
This section describes about the environmental tests performed with 7SR45 Argus Relay under different
conditions.
Table 1-12
Mechanical Tests
Type Test
Reference
Requirement
Degree of Protection
IEC 60529
IP52 front
IP20 rear
Vibration
IEC60255-21-1
1. Vibration Endurance, Class I, Peak
Acceleration 1 gn
X, Y, Z axis (20 sweeps/axis)
2. Vibration Response, Class I, Peak
Acceleration 0.5 gn
X, Y, Z axis (1 sweeps/axis)
Frequency Range : 10 Hz to 150 Hz
Sweep rate : 1 octave/min
Shock and Bump
IEC 60255-21-2
1. Shock response, Class I,
Peak Acceleration 5 gn
X, Y, Z axis (3 per direction)
Total number of shocks: 18
2. Shock withstand, Class I,
Peak Acceleration 15 gn
X, Y, Z axis (3 per direction)
Total number of shocks: 18
3. Bump, Class 1,
Peak Acceleration 10 gn
X, Y, Z axis (1000 per direction)
Total number of Bumps: 6000
Seismic
IEC 60255-21-3
1. In single axis sine sweep in X axis, Class I,
Peak Acceleration 1 gn
2. In single axis sine sweep in Y axis, Class I,
Peak Acceleration 0.5 gn
Frequency Range : 1 Hz to 35 Hz
Sweep rate : 1 octave/minute
Contact Performance IEC 60255-1
(Ref: Std IEC 61810-1)
Making Capacity
Carry continuously
Make and carry
Breaking Capacity
Electrical Endurance: 10000 operations