Chapter 3 - 7SR157 Performance Specification
© 2022 Siemens Protection Devices Limited
Chapter 3 - Page 13 of 18
1.4.3.9
Power Frequency Immunity
IEC 60255-26 & IEC 61000-4-16
IEC 60255-22-7 (withdrawn)
Type
Level
Binary Inputs Common mode (min operate time delay 0ms)
300 V
Differential mode (min operate time delay 10ms)
150 V
1.4.4
Mechanical
1.4.4.1 Vibration (Sinusoidal)
IEC 60255-27 & IEC 60255-21-1 Class I
Type
Level
Variation
Vibration response
0.5 gn
5%
Vibration endurance
1.0 gn
1.4.4.2 Shock and Bump
IEC 60255-27 & IEC 60255-21-2 Class I
Type
Level
Variation
Shock response
5 gn, 11 ms
5%
Shock withstand
15 gn, 11 ms
Bump test
10 gn, 16 ms
1.4.4.3 Seismic
IEC 60255-27 & IEC 60255-21-3 Class I
Type
Level
Variation
Seismic response
X-plane - 3.5mm displacement below crossover freq
(8-9Hz) 1.0gn above
5%
Y-plane - 1.5mm displacement below crossover freq
(8-9Hz) 0.5gn above
1.4.4.4 Mechanical Classification
Type
Level
Durability
> 10
6
operations
Содержание 7SR157 Argus
Страница 1: ...Energy Management 7SR157 Argus Check and System Synchronising Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR157 Contents ...
Страница 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Страница 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Страница 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Страница 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Страница 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Страница 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Страница 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Страница 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Страница 161: ...Chapter 6 7SR157 Commissioning and Maintenance Guide Chapter 6 Page 11 of 14 2016 Siemens Protection Devices Limited ...
Страница 179: ...Siemens Protection Devices 1 ...