7SR157 Technical Manual
Chapter 1 - Page 26 of 38
© 2022 Siemens Protection Devices Limited
4.3 25 System Sync
System Synchronising is enabled via
25 System Sync
and
25 Split Mode
set to SS (System Sync) in the
SYSTEM SYNC MENU. The
25 Split Mode
setting allows the user to determine how the two parts of the network
are reconnected after a split. The options for
25 Split Mode
are CS (Check Sync), SS (System Sync) and COZ
(Close on Zero).
System Synchronising is triggered by a system split. After a split, System Sync will wait for Line and Bus voltages
to realign, before setting
25 InSyncSS
and
25 System Sync Close
outputs.
System Synchronising requires
25 Voltage Check
and
25 System Split
outputs to be set.
25 Voltage Check
is
an output derived from voltage logic, indicating that the line and bus voltages are healthy. Figure 4-1 illustrates
the
25 Voltage Check
Function logic.
The phase angle tolerance between the Line and Bus voltages for being synchronised is set by the
25 System
Sync Angle
setting in the SYSTEM SYNC MENU. The maximum frequency difference between the Line and Bus
voltages is set by
25 System Sync Slip
.
The synchronised conditions must be held for a minimum time of
25 System Sync Timer
setting before
25
InSyncSS
and
25 System Sync Close
outputs are set.
The
25 System Sync Close
output is a pulsed output. The duration of the pulse can be set by adjusting the
25
COZ Close Pulse
setting.
The System Sync inhibit command,
System Sync Inhibit
will inhibit a
25 System Sync Close
output from being
set.
System Sync Inhibit
will not inhibit the
25 InSyncSS
or
25 SS In Progress
outputs from being set.
There are three modes of operation: Auto and Manual and Lockout mode. The selection is made by changing the
25 System Sync Enable
setting.
AUTO
:
25 System Sync Close
output is set when the System synchronizing conditions are met.
MANUAL
:
25 System Sync Close
output is set when System synchronizing conditions are met and a manual
close command is received, via
Start System Sync
input.
LOCKOUT
: The
System Split Lockout
output is set when there is a
25 System Split
event.
The
System Split Lockout
is reset by any of the following:
Reset Lockout Mode
command (via Binary input or comms)
Either the Line or Bus voltages become dead.
The relay HMI
Test/Reset
key is pressed.
For the relay to issue a
25 System Sync Close
output the following conditions have to be met:
25 Line Undervolts
[If enabled] – the line voltage has to be above the
25 Line Undervolts
setting
value for an output to be given.
25 Bus Undervolts
[If enabled] – the bus voltage has to be above the
25 Bus Undervolts
setting
value for an output to be given.
25 Volt Differential
[If enabled] – the percentage difference between the line and bus voltages has
to be less than the
25 Volt Differential
percentage for an output to be given.
25 System Sync Angle
– the phase difference between the line and bus voltages has to be less
than
25 System Sync Angle
setting value and the phase angle has to be decreasing before the
element will issue a valid close signal.
25 System Sync Slip
– the frequency difference between line and bus has to be less than the
25
System Sync Slip
setting value.
25 System Sync Timer
– the phase angle, slip frequency and voltage blocking features have to be
within their parameters for the duration of the
25 System Sync Timer
setting. If either the phase
angle, slip frequency or the voltage elements fall outside of their limits the
25 System Sync Timer
is
reset. If they subsequently come back in then the
25 System Sync Timer
has to time out before a
close output is given. (This ensures that a close output will not be given if there is a transient
disturbance on the system due to e.g. some remote switching operations).
Figure 4-3 illustrates the System Sync Function logic.
Содержание 7SR157 Argus
Страница 1: ...Energy Management 7SR157 Argus Check and System Synchronising Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR157 Contents ...
Страница 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Страница 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Страница 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Страница 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Страница 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Страница 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Страница 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Страница 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Страница 161: ...Chapter 6 7SR157 Commissioning and Maintenance Guide Chapter 6 Page 11 of 14 2016 Siemens Protection Devices Limited ...
Страница 179: ...Siemens Protection Devices 1 ...