7SR157 Technical Manual
Chapter 4 - Page 46 of 58
© 2016 Siemens Protection Devices Limited
Analog inputs are by default returned in a class zero interrogation.
Note, not all points listed here apply to all builds of devices.
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
0 Frequency
0,3
2
4
100.000
1.000
95 Active Setting Group
0,3
2
4
1.000
1.000
162 Phase Diff
0,3
2
4
100.000
1.000
163 Slip Freq
0,3
2
4
100.000
1.000
164 Voltage Diff
0,3
2
4
100.000
1.000
331 V Line Primary
0,3
2
4
0.010
100.000
332 V Bus Primary
0,3
2
4
0.010
100.000
333 V Line Secondary
0,3
2
4
10.000
1.000
334 V Bus Secondary
0,3
2
4
10.000
1.000
335 V Line Max
0,3
2
4
0.010
100.000
336 V Bus Max
0,3
2
4
0.010
100.000
5.4 Additional Settings
The following relay settings are provided for configuration of the DNP 3.0 implementation when available and are
common to all ports using this protocol.
Setting Name
Range/Options
Default
Setting
Notes
Unsolicited
Mode
DISABLED, ENABLED
DISABLED
As Required
Setting is only visible
when any port
Protocol is set to
DNP3.
Destination
Address
0 - 65534
0
As Required
Setting is only
visible when DNP3
Unsolicited Events
set to Enabled.
DNP3
Application
Timeout
5, 6 ... 299, 300
10s
As Required
Setting is only visible
when any port
Protocol is set to
DNP3.
Содержание 7SR157 Argus
Страница 1: ...Energy Management 7SR157 Argus Check and System Synchronising Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR157 Contents ...
Страница 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Страница 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Страница 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Страница 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Страница 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Страница 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Страница 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Страница 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Страница 161: ...Chapter 6 7SR157 Commissioning and Maintenance Guide Chapter 6 Page 11 of 14 2016 Siemens Protection Devices Limited ...
Страница 179: ...Siemens Protection Devices 1 ...