7SR158 Technical Manual
Chapter 3 - Page 14 of 18
© 2022 Siemens Protection Devices Limited
Section 2: Control & Logic Functions
2.1
Voltage Settings (Live and Dead Status)
2.1.1
Live and Dead Status
2.1.1.1 Reference
Parameter
Value
Line Nom Voltage
40, 40.1... 160 V
Bus Nom Voltage
40, 40.1... 160 V
System Frequency
50/60 Hz
25 Live Line
0, 1... 150%
25 Dead Line
0, 1... 150%
25 Live Line
0, 1... 150%
25 Dead Line
0, 1... 150%
2.1.1.2 Operate and Reset Level
Attribute
Value
V
live,act
Live operate level
100% V
live
,
1% V
n
Live reset level
V
dead,act
,
1% V
n
Live Hysteresis level
V
live,act
- 3% V
n
V
dead,act
Dead operate level
100% V
dead
,
1% V
n
Dead reset level
V
live,act
,
1% V
n
Dead Hysteresis level
V
dead,act
- 3% V
n
Repeatability
1%
Variation
-10°C to +55°C
5%
f
nom
± 5%
1%
Содержание 7SR157 Argus
Страница 1: ...Energy Management 7SR157 Argus Check and System Synchronising Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR157 Contents ...
Страница 58: ...7SR158 Technical Manual Chapter 3 Page 2 of 18 2022 Siemens Protection Devices Limited ...
Страница 76: ...7SR157 Technical Manual Chapter 4 Page 2 of 58 2016 Siemens Protection Devices Limited ...
Страница 80: ...7SR157 Technical Manual Chapter 4 Page 6 of 58 2016 Siemens Protection Devices Limited ...
Страница 92: ...7SR157 Technical Manual Chapter 4 Page 18 of 58 2016 Siemens Protection Devices Limited ...
Страница 122: ...7SR157 Technical Manual Chapter 4 Page 48 of 58 2016 Siemens Protection Devices Limited ...
Страница 124: ...7SR157 Technical Manual Chapter 4 Page 50 of 58 2016 Siemens Protection Devices Limited ...
Страница 126: ...7SR157 Technical Manual Chapter 4 Page 52 of 58 2016 Siemens Protection Devices Limited ...
Страница 150: ...7SR157 Technical Manual Chapter 5 Page 18 of 18 2018 Siemens Protection Devices Limited ...
Страница 161: ...Chapter 6 7SR157 Commissioning and Maintenance Guide Chapter 6 Page 11 of 14 2016 Siemens Protection Devices Limited ...
Страница 179: ...Siemens Protection Devices 1 ...