4. Replace the corrosion protection.
5. Reattach the rotor shipping brace, if present.
6. Pack the machine again.
4.11.6
Protection against corrosion
If the machine is stored in dry conditions, then apply the subsequently listed anti-corrosion
measures:
● Storage up to six months:
Apply a coat of corrosion protective compound to all accessible bare metal parts such as
the exposed shaft extension, flange or machine feet.
● Storage for longer than six months:
Apply a coat of anti-corrosion compound which provides long-term protection, e.g.
Tectyl 506.
● Inspect the machine regularly and apply an additional coating of corrosion protection if
necessary.
Document all preservation measures taken so that they can be reversed before the machines
are put back into service.
4.12
Converter operation
The following chapter is relevant only to machines of series 1PQ8 or if the machine was ordered
for operation on the rectifier.
Note
The order number shows whether the machine was ordered for operation with converter: the
9th digit of the order number features the letter "P" or "Q".
4.12.1
Converter operation of explosion-proof machines
The operation of the explosion-proof machine on the frequency converter is permitted, when
the specifications for the speed control range and torque characteristic are observed, and if
winding temperature monitoring is ensured via the integrated temperature sensors in
conjunction with a tripping unit.
Preparations for use
4.12 Converter operation
SIMOTICS TN Series N-compact 1LA8
Operating Instructions 05/2014
39
Содержание 1LA8
Страница 2: ...23 05 2014 10 18 V8 00 ...
Страница 12: ...Table of contents SIMOTICS TN Series N compact 1LA8 12 Operating Instructions 05 2014 ...
Страница 14: ...Introduction 1 1 About these instructions SIMOTICS TN Series N compact 1LA8 14 Operating Instructions 05 2014 ...
Страница 60: ...Assembly 5 3 Installing the machine SIMOTICS TN Series N compact 1LA8 60 Operating Instructions 05 2014 ...
Страница 88: ...Start up 7 7 De energizing SIMOTICS TN Series N compact 1LA8 88 Operating Instructions 05 2014 ...
Страница 100: ...Operation 8 11 faults SIMOTICS TN Series N compact 1LA8 100 Operating Instructions 05 2014 ...
Страница 173: ...AC Declaration of conformity 1LA8 area 22 AA KE NSR _1LA8_1PQ8_1PP8_1LP8 ...