6.3.4
Connecting the grounding conductor
The grounding conductor cross-section of the machine must be in full conformance with the
installation specifications, e.g. according to IEC / EN 60204-1.
Table 6-2
Determining the cross-section of the grounding conductor
Phase conductor cross-section S
[mm²]
Cross-section of grounding conductor
[mm²]
S > 35
S/2
There is a hexagon bolt with a flat washer and a spring washer on the stator frame at the
designated connecting point for the grounding conductor. The grounding conductor can be
connected as follows:
● With stranded cables with cable lugs
● With flat cables with cable end designed accordingly
As an alternative, you can connect the grounding conductor without cable lugs using a terminal
plate at the marked connection point.
Connecting the grounding conductor
● Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free vaseline.
● Arrange the flat washer and spring washer under the bolt head.
● Check that the maximum permissible clamping thickness of 10 mm for the cable lug or strap
is not exceeded.
● Fasten the clamping screw according to the following table. Screw-in depth and tightening
torque are different depending on whether cable lugs or ground terminals are used.
Screw
Screw-in depth
Tightening torque
When using cable lugs
M12 x 25
> 16 mm
38 Nm
M16 x 35
> 20 mm
92 Nm
When using grounding
terminals
M6
> 9 mm
8 Nm
M8
> 12 mm
20 Nm
M10
> 15 mm
40 Nm
M12
> 18 mm
70 Nm
M16
> 20 mm
170 Nm
● Use the connecting terminals designated for the grounding conductor in the terminal box.
See also
Electrical connection
6.3 Preparation
SIMOTICS TN Series N-compact 1LA8
66
Operating Instructions 05/2014
Содержание 1LA8
Страница 2: ...23 05 2014 10 18 V8 00 ...
Страница 12: ...Table of contents SIMOTICS TN Series N compact 1LA8 12 Operating Instructions 05 2014 ...
Страница 14: ...Introduction 1 1 About these instructions SIMOTICS TN Series N compact 1LA8 14 Operating Instructions 05 2014 ...
Страница 60: ...Assembly 5 3 Installing the machine SIMOTICS TN Series N compact 1LA8 60 Operating Instructions 05 2014 ...
Страница 88: ...Start up 7 7 De energizing SIMOTICS TN Series N compact 1LA8 88 Operating Instructions 05 2014 ...
Страница 100: ...Operation 8 11 faults SIMOTICS TN Series N compact 1LA8 100 Operating Instructions 05 2014 ...
Страница 173: ...AC Declaration of conformity 1LA8 area 22 AA KE NSR _1LA8_1PQ8_1PP8_1LP8 ...