Procedure
Ensure that the minimum air clearances of 10 mm and the creepage distance of 20 mm are
maintained for the connection.
1. Open the terminal box and cut the cable to the correct length.
2. Prepare the end of the cable depending on the cable and its use. Make sure that no external
forces are acting on the cable connection.
3. Insulate the conductor ends in such a way that the remaining insulation reaches almost up
to the cable lug.
4. Make sure the terminal clamps
③
,
④
are arranged correctly for the size of the conductor.
Insert the cable into the terminal clamps. Tighten the clamping nuts
⑤
to a tightening torque
of 8 Nm.
5. If you have loosened the terminal body clamping bolts
②
, then retighten them to a torque
of 40 Nm.
For terminal box GT640, the fixing of the terminal element
①
is done using a terminal nut
M12 on the threaded stud of the terminal support with a torque of 20 Nm.
Figure 6-6
Connection using terminal clamps (schematic diagram)
Lug terminal connections may be installed if ordered accordingly, which are suitable for
connecting flexible and stranded conductors without the use of wire end ferrules. If you wish
Electrical connection
6.4 Connection
SIMOTICS TN Series N-compact 1LA8
Operating Instructions 05/2014
73
Содержание 1LA8
Страница 2: ...23 05 2014 10 18 V8 00 ...
Страница 12: ...Table of contents SIMOTICS TN Series N compact 1LA8 12 Operating Instructions 05 2014 ...
Страница 14: ...Introduction 1 1 About these instructions SIMOTICS TN Series N compact 1LA8 14 Operating Instructions 05 2014 ...
Страница 60: ...Assembly 5 3 Installing the machine SIMOTICS TN Series N compact 1LA8 60 Operating Instructions 05 2014 ...
Страница 88: ...Start up 7 7 De energizing SIMOTICS TN Series N compact 1LA8 88 Operating Instructions 05 2014 ...
Страница 100: ...Operation 8 11 faults SIMOTICS TN Series N compact 1LA8 100 Operating Instructions 05 2014 ...
Страница 173: ...AC Declaration of conformity 1LA8 area 22 AA KE NSR _1LA8_1PQ8_1PP8_1LP8 ...