background image

25

6.3.  OPERATING PROCEDURE FOR A PARALLEL SYSTEM 

(ONLY IN 4 TO 10 KVA MODELS).

 

In parallel systems, check that the programming of Output 2 

is the same on all of them to avoid conflicts.

 

The operating procedure established here is for devices 

with a configuration determined by factory default.

 

Check that the load or loads and/or the output circuit 

breakers on the distribution board are ‘Off’. 

 

Turn “On” the input circuit breakers on the distribution or 

manual bypass board and those on each UPS in 4 to 10 kVA.

The UPSs supply output voltage from the internal static 

bypass of each unit. Observe the LCD screen of the control 

panel for any warnings or error information. Measure the 

output voltage at the terminals of each UPS separately to 

check that the voltage difference between them is less 

than 1 V. If the difference is greater than 1 V, check the 

connection and the associated instructions.

 

If everything is correct, proceed. Press the ‘ON’ button on 

all of the UPSs for more than 2 seconds and each of them 

will start up. All of the UPSs will transfer to ‘Normal mode’.

Measure the output voltage at the terminals of each UPS 

separately to check that the voltage difference between 

them is less than 0.5 V. If the difference is greater than 1 V, 

the UPSs will need to be adjusted (contact 

T.S.S.

).

 

If everything is correct, proceed. Press the ‘OFF’ button for 

more than 2 seconds on all of the UPSs and each of them 

will begin to shut down the device.

Turn the input circuit breakers on the distribution or 

manual bypass board to ‘On’. The output terminals on the 

distribution board will be under potential through the static 

bypass of the device.

 

Press the ‘ON’ button for more than 0.5 seconds on all of 

the UPSs and each one of them will begin to start up in 

order to finally leave the system in parallel operation in 

‘Normal mode’.

 

Start the load or loads.

 

Do not leave a floating UPS with respect to the 

others. There must always be a connection between 

the neutrals, either input or output. Do not open the input 

and output circuit breakers of a UPS at the same time on 

the distribution board while the UPS running. Otherwise, a 

fault in the UPS may occur and the connected loads may 

shut down 

6.4.  HOW TO ADD A UPS TO A SYSTEM IN PARALLEL 

OPERATION OR TO A FUNCTIONING SINGLE UPS 

(ONLY IN 4 TO 10 KVA MODELS).

 

To operate the parallel system, it is necessary to have a 

manual bypass board for the parallel system.

In the event of not having one, the shutdown of the entire 

system and the loads powered by it must be anticipated.

 

The steps to follow are for the addition of a device to a 

system with two units. To incorporate a device into a 

system with only one UPS, proceed in the same way.

 

The distribution board must have input and output switches 

for each UPS, in addition to the one for the manual bypass. 

Otherwise, it will be necessary to adapt the board or 

acquire a new one if it has not been previously anticipated.

 

Since it is necessary to change the parallel bus connection 

to incorporate the new device into the system (cable 

with DB15 connectors), it will be necessary to switch the 

powering of the loads to the manual bypass. 

Proceed as follows:

 

ˆ

Press the ‘OFF’ button on all of the UPSs for more than 

2 seconds to shut down the inverter in all of them. The 

audible alarm will sound for 1 second. The devices 

that make up the current parallel system will switch to 

‘Bypass mode’.

 

ˆ

Switch the devices to manual bypass using the 

following procedure:

1. 

Remove the mechanical lock on the distribution 

board’s manual bypass switch or disconnector and 

turn it to ‘On’.

2. 

Remove the protective cover of the manual bypass 

switch, which is located at the back of each unit, 

and turn all of the switches to ‘BYPASS’.

 

ˆ

 

Take into consideration that in ‘Bypass mode’ or 

with the switch turned to ‘BYPASS’, the loads 

will be exposed to voltage and frequency variations and 

cuts or micro-cuts in mains power, so, if possible, it is 

recommended to choose a day with lower probability of 

failure (days without fluctuations, days without storms, 

etc.) and a certain speed in the process.

 

ˆ

Turn the input circuit breakers of each device to ‘Off’.

 

ˆ

Turn the input and output circuit breakers of the board 

to ‘Off’.

 

Before incorporating the new TWIN RT2 into the system, 

carry out the appropriate steps to leave it in the same 

condition as the others (input switch turned to ‘Off’ and 

manual bypass switch without protective cover turned to 

‘BYPASS’).

 

Incorporate the new UPS to the system following the 

procedure established in section 5.2.8.2 for connection in 

parallel.

 

Disconnect the communication bus between the first and 

last device, and reconnect it including the new UPS. The 

bus must be closed for proper operation.

 

Turn the input circuit breakers of each UPS on the 

distribution board to ‘On’.

 

Turn the input circuit breakers of each UPS to ‘On’.

Turn the internal manual bypass switch of each UPS to UPS.

The output switches of each UPS on the distribution board 

must be open.

Fit the switch lock cover of each UPS

The UPSs supply output voltage from the internal static 

bypass of each unit. Observe the LCD screen of the control 

panel for any warnings or error information. Measure the 

output voltage at the terminals of each UPS separately to 

check that the voltage difference between them is less 

than 1 V. If the difference is greater than 1 V, check the 

connection and the associated instructions.

 

If everything is correct, proceed. Press the ‘ON’ button on 

all of the UPSs for more than 2 seconds and each of them 

will start up. All of the UPSs will transfer to ‘Normal mode’.

Measure the output voltage at the terminals of each UPS 

separately to check that the voltage difference between 

them is less than 0.5 V. If the difference is greater than 1 V, 

the UPSs will need to be adjusted (contact 

T.S.S.

).

USER MANUAL        

 

 

 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 

Содержание SLC TWIN RT2 LION

Страница 1: ...SLC TWIN RT2 0 7 10 kVA UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL Industriestrasse 17 Tel 061 926 90 60 www sicotec ch CH 4415 Lausen Fax 061 926 90 66 usv sicotec ch SICOTEC AG...

Страница 2: ...ower typemountingwithPDU 5 1 5 7 Rackmountingin19 cabinetwithPDU 5 1 5 8 Preliminaryconsiderationsbeforeconnection 5 1 5 9 Preliminary considerations before connection regarding the batteriesandtheirp...

Страница 3: ...ingmode Descriptionofstate 7 2 4 3 Warningoralertcodes 7 2 4 4 Errororfaultcodes 7 2 4 5 Warningoralertindicators 7 3 CONTROLPANELFOR4KVATO10KVAMODELS 7 3 1 Audiblealarms 7 3 2 Opticalindications 7 3...

Страница 4: ...hough no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images included in thi...

Страница 5: ...s of installation and commissioning to be performed in a simple and orderly manner without having any doubts whatsoever Finally once the equipment is installed and operating it is recommended to save...

Страница 6: ...may cause radio interference in which case the user must take additional measures SLC TWIN RT2 4 10 kVA This is a category C3 UPS This is a product for commercial and industrial application in the se...

Страница 7: ...belling on the equipment itself will always prevail The nameplate of the device shows all of the values relating to its main properties and characteristics Act accordingly for its installation 0 7 to...

Страница 8: ...mable at disconnection for non critical loads Connector for connection to external battery module Standard and B1 3 kVA models COM port USB RS232 COM port AC power IEC connector Smart slot protective...

Страница 9: ...nnector VDC protection Battery module connector Fig 3 Rear view of battery modules for extended backups PDU for 4 to 6 kVA devices Output circuit breaker Output IEC connectors Output circuit breaker O...

Страница 10: ...hout batteries but with a space reserved for installation in the same box for models whose standard version specifies this For other models the battery pack will be installed in the manner considered...

Страница 11: ...f the blockage or fault remains contact T S S With the inverter shut down the output supplies mains power directly through the static bypass of the device provided that it has AC input power Frequency...

Страница 12: ...interruptions to the power supply of the protected system while preventing unnecessary hazards for the technical personnel 4 5 3 Communication card The UPS features a slot at the rear for inserting o...

Страница 13: ...ry module for 0 7 to 3 kVA UPS 1 battery module Information for warranty registration 2 metal pieces for use as handles and screws for installing the unit in a rack cabinet 2 plastic pieces to extend...

Страница 14: ...ance is considerable it is recommended to transport the device in its packaging to the installation site and then unpack it 5 1 5 Siting immobilising and considerations All TWIN RT2 series UPSs are de...

Страница 15: ...stallation by the user Mount the guides at the required height ensuring correct tightening of the fixing screws and appropriate fitting in the machining according to each case Place the device onto th...

Страница 16: ...pper or lower part of the cabinet it is recommended that two people carry out the installation operations Fix the UPS and the battery module to the cabinet frame by means of the screws supplied with t...

Страница 17: ...exception The cross section of the cables must always be considered in relation to the size of the terminals of the switches so that they are correctly fastened across their entire cross section for...

Страница 18: ...ting systems in parallel only in models 3 kVA To access the signal block it is necessary to remove its protective cover Slot for the integration of one of the optional electronic communication units R...

Страница 19: ...C connectors indicated in Fig 2 as critical loads will be reserved Take into account that they are set by default as critical loads The 3 kVA models also have a 16A IEC connector that enables the conn...

Страница 20: ...tage to the input terminals Make sure that all of the loads connected to the UPS are only connected to its earth connection terminal Failure to limit the earthing of the load or loads and battery modu...

Страница 21: ...erent earths of the control of each UPS In the event of acquiring a manual bypass board through another conduit check that it has this auxiliary contact and connect it to the terminal block of the UPS...

Страница 22: ...difference in length between the input and output cables of the device must be less than 20 When the distance between the UPSs in parallel and the circuit breaker board is more than 20 metres the diff...

Страница 23: ...View of ViewPower s main screen Installation procedure Go to the web page http support salicru com Select the required operating system and follow the instructions described on the web page to downlo...

Страница 24: ...output protections to On Turn the battery switch to On models B0 and B1 Turn the device s input circuit breaker to On Press the ON button for more than 2 seconds the audible alarm will sound for 1 se...

Страница 25: ...e manual bypass Otherwise it will be necessary to adapt the board or acquire a new one if it has not been previously anticipated Since it is necessary to change the parallel bus connection to incorpor...

Страница 26: ...accidents To prevent incorrect operations it is necessary to fit the mechanical lock and the covers of the manual bypass mechanisms and their fixing screws Press the ON button on all of the UPSs for...

Страница 27: ...cates the charge level connected to the output as a by displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P...

Страница 28: ...ESC Escape HLS HLS Upper voltage limit for transfer to battery mode LLS LLS Lower voltage limit for transfer to battery mode AO AO EPO normally open AC AC EPO normally closed EAT EAt Estimated backup...

Страница 29: ...de it will move downwards through the menu structure in relation to the point where it is located accessing the following variable with each press OFF ENTER UPS shutdown Press this button for at least...

Страница 30: ...related to the capacity of the battery pack The charger will adapt the charging factor automatically according to the value of the total capacity entered up to the maximum of the current that is poss...

Страница 31: ...tput frequency of 50 Hz CF 60 1 CF with output frequency of 60 Hz 1 With parameter 02 ENA the CF 50 or CF 60 variables are displayed instead of BAT 50 or BAT 60 DIS ECO mode disabled ENA ECO mode enab...

Страница 32: ...output voltage from the bypass in ECO mode energy saving LCD display CF mode Description When the input frequency is between 46 and 64 Hz the UPS can be set to a constant output frequency of 50 or 60...

Страница 33: ...oo high 28 Battery voltage too low 2A Battery charger short circuited at its output 41 Overtemperature 43 Output overload 45 Charger fault 49 Input overcurrent Tab 13 Error or fault code 7 2 4 5 Warni...

Страница 34: ...u structure to the previous variable in relation to the point where it is located ON Starting up the UPS Press the button for at least 2 seconds Confirmation of selection Press this button to confirm...

Страница 35: ...options Tab 18 Parameter 1 codes list Description and settings Code 01 Output voltage Fig 27 Parameter 3 setting Output voltage It is possible to choose one of the following values for the output volt...

Страница 36: ...ss enabled When selected bypass mode is enabled DIS Bypass disabled If selected automatic bypass is permitted but not manual switch to bypass At this point manual switch to bypass is understood as bei...

Страница 37: ...000 TWIN RT2 device with an external battery pack of 45 Ah belonging to it 45 Ah 7 Ah 6 4 When rounding down value 6 must be entered in parameter 3 The basic reason for adjusting the setting is as fol...

Страница 38: ...e regulation ranges and ECO mode is activated the UPS supplies the output voltage from the bypass in ECO mode energy saving LCD display ECO CF mode Description When the output frequency is selected as...

Страница 39: ...30 minutes 3A Maintenance switch cover open 3D Bypass not available 3E Start up fault Tab 20 Warning or alert code 7 3 4 4 Error or fault codes Code Error or fault description 01 DC bus start up faul...

Страница 40: ...which is in turn connected to earth any metal part of the device Repair and or maintenance work must be carried out by our T S S except for the replacement of batteries which can be performed by quali...

Страница 41: ...ds from the output sockets After repeated overloads the UPS is locked in Bypass mode The connected loads are powered directly from the mains Disconnect the excess loads from the output sockets shut do...

Страница 42: ...he following fault codes 01 02 03 04 11 12 13 14 1A 21 24 35 36 41 42 or 43 are displayed on the LCD display and the audible alarm sounds continuously An internal fault has occurred in the UPS This is...

Страница 43: ...0 91 93 Performance at full load in ECO mode 95 96 97 99 Overload in line mode 110 130 5 min 100 110 2 min 130 140 30 sec 110 130 1 min 140 150 1 5 sec 130 1 sec 150 100 ms Overload in battery mode 11...

Страница 44: ...ill be 78 of the rated 6 As a frequency converter the power supplied will be 60 of the rated DSP Digital signal processor A DSP is a processor or microprocessor based system that has a set of instruct...

Страница 45: ...ing through the visible light spectrum to infrared the latter called IRED infra red emitting diode Circuit breaker A circuit breaker is a device capable of interrupting the electrical current of a cir...

Страница 46: ...46 SALICRU...

Страница 47: ...47 USER MANUAL...

Страница 48: ......

Отзывы: