8.2.1.  Troubleshooting guide for devices up to 3 kVA.

Symptom

Possible cause

Solution

No alarms or indications on the LCD display and mains 

voltage normal. 

The power cable is not connected correctly.

Check that the power cables are firmly connected to 

the mains. 

The power cable is connected to an IEC output connector 

on the UPS.

Correctly connect the power cable to the respective 

IEC connector.

Icon 

 and warning code 

 flash on the LCD 

display and the audible alarm modulated every second 

is active.

The EPO function is activated.

Close the EPO signal circuit to deactivate it. 

Icon 

 and warning code 

 flash on the LCD 

display and the audible alarm modulated every two 

seconds is active.

Neutral earth fault detection. Inverted phase and neutral 

input cables.

Disconnect the input plug from the AC power socket 

and invert the connection of the phase and the supply 

neutral (rotate the plug 180º).

Icon 

 and warning code 

 flash on the LCD 

display and the audible alarm modulated every two 

seconds is active.

The internal or external batteries are badly connected

Check that all batteries are properly connected.

Fault code 27 and the 

BATT FAULT

 message 

are shown on the LCD display. The alarm sounds 

continuously.

The voltage of the batteries is too high or the charger is 

faulty.

Contact the distributor or seller or, failing that, our 

T.S.S.

Fault code 28 and the 

BATT FAULT

 message are 

shown on the LCD display. The audible alarm sounds 

continuously.

The voltage of the batteries is too low or the charger is 

faulty.

Contact the distributor or seller or, failing that, our 

T.S.S.

Icon 

 and warning code 

 flash 

on the LCD display and the audible alarm modulated 

every second is active.

The UPS is overloaded.

Disconnect the excess loads from the output sockets.

The UPS is overloaded. The connected loads are powered 

directly from the mains through the Bypass.

Disconnect the excess loads from the output sockets.

After repeated overloads, the UPS is locked in Bypass 

mode. The connected loads are powered directly from the 

mains.

Disconnect the excess loads from the output sockets, 

shut down the device and restart it.

Fault code 49 is shown on the LCD display. The 

audible alarm sounds continuously.

UPS input overcurrent.

Disconnect the excess loads from the output sockets.

Fault code 43 is shown on the LCD display. The 

audible alarm sounds continuously.

The UPS shuts down automatically as a result of an 

overload in the output of the device.

Disconnect the excess loads from the output sockets 

and restart it.

Fault code 14 is shown on the LCD display. The 

audible alarm sounds continuously.

The UPS shuts down automatically as a result of a short 

circuit in the output.

Check the output wiring and that the connected loads 

are not short-circuited

Fault codes 01, 02, 03, 11, 12, 13 and 41 are shown 

on the LCD display. The audible alarm sounds 

continuously.

An internal fault has occurred in the UPS. This is due to one 

of two possibilities:

1. The load is still powered, but directly from the mains 

through the bypass.

2. The load is no longer powered.

Contact the distributor or seller or, failing that, our 

T.S.S.

The backup time is shorter than expected.

The batteries do not charge completely.

Charge the batteries for at least 5 h and then check 

their charge state. If the problem persists, contact the 

distributor or seller or, failing that, our T.S.S.

Faulty batteries.

Contact the distributor or seller or, failing that, our 

T.S.S. for battery replacement.

Fault code 2A is shown on the LCD display. The 

audible alarm sounds continuously.

Charger short-circuited at its output.

Check whether the connection of the external battery 

pack connected to the UPS is short-circuited.

Fault code 45 is shown on the LCD display. At the 

same time, the audible alarm sounds continuously.

The charger does not provide output and the battery voltage 

is less than 10 V per element.

Contact the distributor or seller or, failing that, our 

T.S.S.

Tab. 23. 

Troubleshooting guide.

USER MANUAL        

 

 

 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 

Содержание SLC TWIN RT2 LION

Страница 1: ...SLC TWIN RT2 0 7 10 kVA UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL Industriestrasse 17 Tel 061 926 90 60 www sicotec ch CH 4415 Lausen Fax 061 926 90 66 usv sicotec ch SICOTEC AG...

Страница 2: ...ower typemountingwithPDU 5 1 5 7 Rackmountingin19 cabinetwithPDU 5 1 5 8 Preliminaryconsiderationsbeforeconnection 5 1 5 9 Preliminary considerations before connection regarding the batteriesandtheirp...

Страница 3: ...ingmode Descriptionofstate 7 2 4 3 Warningoralertcodes 7 2 4 4 Errororfaultcodes 7 2 4 5 Warningoralertindicators 7 3 CONTROLPANELFOR4KVATO10KVAMODELS 7 3 1 Audiblealarms 7 3 2 Opticalindications 7 3...

Страница 4: ...hough no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images included in thi...

Страница 5: ...s of installation and commissioning to be performed in a simple and orderly manner without having any doubts whatsoever Finally once the equipment is installed and operating it is recommended to save...

Страница 6: ...may cause radio interference in which case the user must take additional measures SLC TWIN RT2 4 10 kVA This is a category C3 UPS This is a product for commercial and industrial application in the se...

Страница 7: ...belling on the equipment itself will always prevail The nameplate of the device shows all of the values relating to its main properties and characteristics Act accordingly for its installation 0 7 to...

Страница 8: ...mable at disconnection for non critical loads Connector for connection to external battery module Standard and B1 3 kVA models COM port USB RS232 COM port AC power IEC connector Smart slot protective...

Страница 9: ...nnector VDC protection Battery module connector Fig 3 Rear view of battery modules for extended backups PDU for 4 to 6 kVA devices Output circuit breaker Output IEC connectors Output circuit breaker O...

Страница 10: ...hout batteries but with a space reserved for installation in the same box for models whose standard version specifies this For other models the battery pack will be installed in the manner considered...

Страница 11: ...f the blockage or fault remains contact T S S With the inverter shut down the output supplies mains power directly through the static bypass of the device provided that it has AC input power Frequency...

Страница 12: ...interruptions to the power supply of the protected system while preventing unnecessary hazards for the technical personnel 4 5 3 Communication card The UPS features a slot at the rear for inserting o...

Страница 13: ...ry module for 0 7 to 3 kVA UPS 1 battery module Information for warranty registration 2 metal pieces for use as handles and screws for installing the unit in a rack cabinet 2 plastic pieces to extend...

Страница 14: ...ance is considerable it is recommended to transport the device in its packaging to the installation site and then unpack it 5 1 5 Siting immobilising and considerations All TWIN RT2 series UPSs are de...

Страница 15: ...stallation by the user Mount the guides at the required height ensuring correct tightening of the fixing screws and appropriate fitting in the machining according to each case Place the device onto th...

Страница 16: ...pper or lower part of the cabinet it is recommended that two people carry out the installation operations Fix the UPS and the battery module to the cabinet frame by means of the screws supplied with t...

Страница 17: ...exception The cross section of the cables must always be considered in relation to the size of the terminals of the switches so that they are correctly fastened across their entire cross section for...

Страница 18: ...ting systems in parallel only in models 3 kVA To access the signal block it is necessary to remove its protective cover Slot for the integration of one of the optional electronic communication units R...

Страница 19: ...C connectors indicated in Fig 2 as critical loads will be reserved Take into account that they are set by default as critical loads The 3 kVA models also have a 16A IEC connector that enables the conn...

Страница 20: ...tage to the input terminals Make sure that all of the loads connected to the UPS are only connected to its earth connection terminal Failure to limit the earthing of the load or loads and battery modu...

Страница 21: ...erent earths of the control of each UPS In the event of acquiring a manual bypass board through another conduit check that it has this auxiliary contact and connect it to the terminal block of the UPS...

Страница 22: ...difference in length between the input and output cables of the device must be less than 20 When the distance between the UPSs in parallel and the circuit breaker board is more than 20 metres the diff...

Страница 23: ...View of ViewPower s main screen Installation procedure Go to the web page http support salicru com Select the required operating system and follow the instructions described on the web page to downlo...

Страница 24: ...output protections to On Turn the battery switch to On models B0 and B1 Turn the device s input circuit breaker to On Press the ON button for more than 2 seconds the audible alarm will sound for 1 se...

Страница 25: ...e manual bypass Otherwise it will be necessary to adapt the board or acquire a new one if it has not been previously anticipated Since it is necessary to change the parallel bus connection to incorpor...

Страница 26: ...accidents To prevent incorrect operations it is necessary to fit the mechanical lock and the covers of the manual bypass mechanisms and their fixing screws Press the ON button on all of the UPSs for...

Страница 27: ...cates the charge level connected to the output as a by displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P...

Страница 28: ...ESC Escape HLS HLS Upper voltage limit for transfer to battery mode LLS LLS Lower voltage limit for transfer to battery mode AO AO EPO normally open AC AC EPO normally closed EAT EAt Estimated backup...

Страница 29: ...de it will move downwards through the menu structure in relation to the point where it is located accessing the following variable with each press OFF ENTER UPS shutdown Press this button for at least...

Страница 30: ...related to the capacity of the battery pack The charger will adapt the charging factor automatically according to the value of the total capacity entered up to the maximum of the current that is poss...

Страница 31: ...tput frequency of 50 Hz CF 60 1 CF with output frequency of 60 Hz 1 With parameter 02 ENA the CF 50 or CF 60 variables are displayed instead of BAT 50 or BAT 60 DIS ECO mode disabled ENA ECO mode enab...

Страница 32: ...output voltage from the bypass in ECO mode energy saving LCD display CF mode Description When the input frequency is between 46 and 64 Hz the UPS can be set to a constant output frequency of 50 or 60...

Страница 33: ...oo high 28 Battery voltage too low 2A Battery charger short circuited at its output 41 Overtemperature 43 Output overload 45 Charger fault 49 Input overcurrent Tab 13 Error or fault code 7 2 4 5 Warni...

Страница 34: ...u structure to the previous variable in relation to the point where it is located ON Starting up the UPS Press the button for at least 2 seconds Confirmation of selection Press this button to confirm...

Страница 35: ...options Tab 18 Parameter 1 codes list Description and settings Code 01 Output voltage Fig 27 Parameter 3 setting Output voltage It is possible to choose one of the following values for the output volt...

Страница 36: ...ss enabled When selected bypass mode is enabled DIS Bypass disabled If selected automatic bypass is permitted but not manual switch to bypass At this point manual switch to bypass is understood as bei...

Страница 37: ...000 TWIN RT2 device with an external battery pack of 45 Ah belonging to it 45 Ah 7 Ah 6 4 When rounding down value 6 must be entered in parameter 3 The basic reason for adjusting the setting is as fol...

Страница 38: ...e regulation ranges and ECO mode is activated the UPS supplies the output voltage from the bypass in ECO mode energy saving LCD display ECO CF mode Description When the output frequency is selected as...

Страница 39: ...30 minutes 3A Maintenance switch cover open 3D Bypass not available 3E Start up fault Tab 20 Warning or alert code 7 3 4 4 Error or fault codes Code Error or fault description 01 DC bus start up faul...

Страница 40: ...which is in turn connected to earth any metal part of the device Repair and or maintenance work must be carried out by our T S S except for the replacement of batteries which can be performed by quali...

Страница 41: ...ds from the output sockets After repeated overloads the UPS is locked in Bypass mode The connected loads are powered directly from the mains Disconnect the excess loads from the output sockets shut do...

Страница 42: ...he following fault codes 01 02 03 04 11 12 13 14 1A 21 24 35 36 41 42 or 43 are displayed on the LCD display and the audible alarm sounds continuously An internal fault has occurred in the UPS This is...

Страница 43: ...0 91 93 Performance at full load in ECO mode 95 96 97 99 Overload in line mode 110 130 5 min 100 110 2 min 130 140 30 sec 110 130 1 min 140 150 1 5 sec 130 1 sec 150 100 ms Overload in battery mode 11...

Страница 44: ...ill be 78 of the rated 6 As a frequency converter the power supplied will be 60 of the rated DSP Digital signal processor A DSP is a processor or microprocessor based system that has a set of instruct...

Страница 45: ...ing through the visible light spectrum to infrared the latter called IRED infra red emitting diode Circuit breaker A circuit breaker is a device capable of interrupting the electrical current of a cir...

Страница 46: ...46 SALICRU...

Страница 47: ...47 USER MANUAL...

Страница 48: ......

Отзывы: