background image

24

6.  OPERATION.

6.1.  START-UP.

6.1.1.  Checks before start-up.

 

Make sure that all of the connections have been made 

correctly and with sufficient tightening torque, following 

the instructions on the labelling of the device and in 

Chapter 5.

 

Check that the UPS and battery module or modules switches 

are ‘Off’.

 

Make sure that all loads are ‘Off’.

Shut down the connected loads before starting the 

UPS and start the loads, one by one, only when the 

UPS is running. Before shutting down the UPS, check that 

all of the loads are ‘Off’.

 

It is very important to proceed in the established order.

 

For views of the UPS, see Fig. 1 to Fig. 3.

 

In Fig. 18 , a distribution board with manual bypass is re-

presented conceptually for a parallel system, representative 

for a single device, with the number of switches adapted.

6.2.  UPS START-UP AND SHUTDOWN.

6.2.1.  UPS start-up with mains voltage.

 

Check that the power connection is correct.

 

Supply voltage to the device (turn the input protection on 

the distribution board or manual bypass to ‘On’. If the board 

has an output switch, turn it to  ‘On’.

 

Turn the battery switch to ‘On’ (models B0 and B1).

 

In 4 to 10 kVA models, turn the UPS’s input circuit breaker 

located at the back of the device to ‘On’.

The output terminals will have voltage through the 

device’s internal static bypass block.

The fan or fans, depending on the model, will start to 

function. 

Then the main start screen will be displayed after a test of 

the device.

 

Press the ‘ON’ button for more than 2 seconds, the audible 

alarm will sound for 1 second and the UPS will start up.

 

The UPS is set to ‘Normal mode’ after a few seconds. If the 

mains voltage is incorrect, the UPS will switch to ‘Battery 

mode’, without interrupting the power supply at the output 

terminals.

 

Start the load or loads, making sure that the rated power of 

the device is not exceeded.

6.2.2.  UPS start-up without mains voltage.

 

If it has a distribution board, turn the input and output 

protections to ‘On’.

 

Turn the battery switch to ‘On’ (models B0 and B1).

 

Turn the device’s input circuit breaker to ‘On’.

 

Press the ‘ON’ button for more than 2 seconds, the audible 

alarm will sound for 1 second and the UPS will start up.

The fan or fans, depending on the model, will start to 

function.

Then the main start screen will be displayed after a test of 

the device.

On the 4 to 10 kVA models, it is necessary to press the ‘ON’ 

button for a second time, about 5 to 7 seconds after the first 

press, for longer than 2 seconds.

 

The UPS is set to ‘Battery mode’ after a few seconds. 

Depending on the level of charge of the batteries, the 

residual backup available may be very limited. Consider the 

risk involved in operating without mains and discharged 

batteries.

If the mains voltage returns, the UPS will transfer to 

‘Normal mode’ without interrupting the power supply at 

the output terminals.

 

Start the load or loads, making sure that the rated power of 

the device is not exceeded.

6.2.3.  UPS shutdown with mains voltage.

 

Shut down the load or loads.

 

Press the ‘OFF’ button for more than 2 seconds to shut down 

the inverter. The audible alarm will sound for 1 second. The 

device will be set to ‘Bypass mode’.

The output terminals will have voltage through the 

device’s internal static bypass block.

 

To cut the UPS’s output voltage:

 

ˆ

Disconnect the input plug of the power socket on 

models up to 3 kVA and from 4 to 10 kVA and turn the 

input circuit breaker located at the back of the device 

to ‘Off’.

 

ˆ

Or simply turn the input and output protections of the 

UPS’s distribution board on any model to ‘Off’.

A few seconds later, the LCD screen turns off and the entire 

device will be out of service.

6.2.4.  UPS shutdown without mains voltage.

 

Shut down the load or loads.

 

Press the ‘OFF’ button for more than 2 seconds to shut down 

the inverter. The audible alarm will sound for 1 second. The 

device will leave the output terminals without voltage.

A few seconds later, the LCD screen turns off and the entire 

device will be out of service.

 

To leave the assembly completely isolated, turn the input 

and output switches of the board to ‘Off’.

 

 

 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 

Содержание SLC TWIN RT2 LION

Страница 1: ...SLC TWIN RT2 0 7 10 kVA UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL Industriestrasse 17 Tel 061 926 90 60 www sicotec ch CH 4415 Lausen Fax 061 926 90 66 usv sicotec ch SICOTEC AG...

Страница 2: ...ower typemountingwithPDU 5 1 5 7 Rackmountingin19 cabinetwithPDU 5 1 5 8 Preliminaryconsiderationsbeforeconnection 5 1 5 9 Preliminary considerations before connection regarding the batteriesandtheirp...

Страница 3: ...ingmode Descriptionofstate 7 2 4 3 Warningoralertcodes 7 2 4 4 Errororfaultcodes 7 2 4 5 Warningoralertindicators 7 3 CONTROLPANELFOR4KVATO10KVAMODELS 7 3 1 Audiblealarms 7 3 2 Opticalindications 7 3...

Страница 4: ...hough no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images included in thi...

Страница 5: ...s of installation and commissioning to be performed in a simple and orderly manner without having any doubts whatsoever Finally once the equipment is installed and operating it is recommended to save...

Страница 6: ...may cause radio interference in which case the user must take additional measures SLC TWIN RT2 4 10 kVA This is a category C3 UPS This is a product for commercial and industrial application in the se...

Страница 7: ...belling on the equipment itself will always prevail The nameplate of the device shows all of the values relating to its main properties and characteristics Act accordingly for its installation 0 7 to...

Страница 8: ...mable at disconnection for non critical loads Connector for connection to external battery module Standard and B1 3 kVA models COM port USB RS232 COM port AC power IEC connector Smart slot protective...

Страница 9: ...nnector VDC protection Battery module connector Fig 3 Rear view of battery modules for extended backups PDU for 4 to 6 kVA devices Output circuit breaker Output IEC connectors Output circuit breaker O...

Страница 10: ...hout batteries but with a space reserved for installation in the same box for models whose standard version specifies this For other models the battery pack will be installed in the manner considered...

Страница 11: ...f the blockage or fault remains contact T S S With the inverter shut down the output supplies mains power directly through the static bypass of the device provided that it has AC input power Frequency...

Страница 12: ...interruptions to the power supply of the protected system while preventing unnecessary hazards for the technical personnel 4 5 3 Communication card The UPS features a slot at the rear for inserting o...

Страница 13: ...ry module for 0 7 to 3 kVA UPS 1 battery module Information for warranty registration 2 metal pieces for use as handles and screws for installing the unit in a rack cabinet 2 plastic pieces to extend...

Страница 14: ...ance is considerable it is recommended to transport the device in its packaging to the installation site and then unpack it 5 1 5 Siting immobilising and considerations All TWIN RT2 series UPSs are de...

Страница 15: ...stallation by the user Mount the guides at the required height ensuring correct tightening of the fixing screws and appropriate fitting in the machining according to each case Place the device onto th...

Страница 16: ...pper or lower part of the cabinet it is recommended that two people carry out the installation operations Fix the UPS and the battery module to the cabinet frame by means of the screws supplied with t...

Страница 17: ...exception The cross section of the cables must always be considered in relation to the size of the terminals of the switches so that they are correctly fastened across their entire cross section for...

Страница 18: ...ting systems in parallel only in models 3 kVA To access the signal block it is necessary to remove its protective cover Slot for the integration of one of the optional electronic communication units R...

Страница 19: ...C connectors indicated in Fig 2 as critical loads will be reserved Take into account that they are set by default as critical loads The 3 kVA models also have a 16A IEC connector that enables the conn...

Страница 20: ...tage to the input terminals Make sure that all of the loads connected to the UPS are only connected to its earth connection terminal Failure to limit the earthing of the load or loads and battery modu...

Страница 21: ...erent earths of the control of each UPS In the event of acquiring a manual bypass board through another conduit check that it has this auxiliary contact and connect it to the terminal block of the UPS...

Страница 22: ...difference in length between the input and output cables of the device must be less than 20 When the distance between the UPSs in parallel and the circuit breaker board is more than 20 metres the diff...

Страница 23: ...View of ViewPower s main screen Installation procedure Go to the web page http support salicru com Select the required operating system and follow the instructions described on the web page to downlo...

Страница 24: ...output protections to On Turn the battery switch to On models B0 and B1 Turn the device s input circuit breaker to On Press the ON button for more than 2 seconds the audible alarm will sound for 1 se...

Страница 25: ...e manual bypass Otherwise it will be necessary to adapt the board or acquire a new one if it has not been previously anticipated Since it is necessary to change the parallel bus connection to incorpor...

Страница 26: ...accidents To prevent incorrect operations it is necessary to fit the mechanical lock and the covers of the manual bypass mechanisms and their fixing screws Press the ON button on all of the UPSs for...

Страница 27: ...cates the charge level connected to the output as a by displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P...

Страница 28: ...ESC Escape HLS HLS Upper voltage limit for transfer to battery mode LLS LLS Lower voltage limit for transfer to battery mode AO AO EPO normally open AC AC EPO normally closed EAT EAt Estimated backup...

Страница 29: ...de it will move downwards through the menu structure in relation to the point where it is located accessing the following variable with each press OFF ENTER UPS shutdown Press this button for at least...

Страница 30: ...related to the capacity of the battery pack The charger will adapt the charging factor automatically according to the value of the total capacity entered up to the maximum of the current that is poss...

Страница 31: ...tput frequency of 50 Hz CF 60 1 CF with output frequency of 60 Hz 1 With parameter 02 ENA the CF 50 or CF 60 variables are displayed instead of BAT 50 or BAT 60 DIS ECO mode disabled ENA ECO mode enab...

Страница 32: ...output voltage from the bypass in ECO mode energy saving LCD display CF mode Description When the input frequency is between 46 and 64 Hz the UPS can be set to a constant output frequency of 50 or 60...

Страница 33: ...oo high 28 Battery voltage too low 2A Battery charger short circuited at its output 41 Overtemperature 43 Output overload 45 Charger fault 49 Input overcurrent Tab 13 Error or fault code 7 2 4 5 Warni...

Страница 34: ...u structure to the previous variable in relation to the point where it is located ON Starting up the UPS Press the button for at least 2 seconds Confirmation of selection Press this button to confirm...

Страница 35: ...options Tab 18 Parameter 1 codes list Description and settings Code 01 Output voltage Fig 27 Parameter 3 setting Output voltage It is possible to choose one of the following values for the output volt...

Страница 36: ...ss enabled When selected bypass mode is enabled DIS Bypass disabled If selected automatic bypass is permitted but not manual switch to bypass At this point manual switch to bypass is understood as bei...

Страница 37: ...000 TWIN RT2 device with an external battery pack of 45 Ah belonging to it 45 Ah 7 Ah 6 4 When rounding down value 6 must be entered in parameter 3 The basic reason for adjusting the setting is as fol...

Страница 38: ...e regulation ranges and ECO mode is activated the UPS supplies the output voltage from the bypass in ECO mode energy saving LCD display ECO CF mode Description When the output frequency is selected as...

Страница 39: ...30 minutes 3A Maintenance switch cover open 3D Bypass not available 3E Start up fault Tab 20 Warning or alert code 7 3 4 4 Error or fault codes Code Error or fault description 01 DC bus start up faul...

Страница 40: ...which is in turn connected to earth any metal part of the device Repair and or maintenance work must be carried out by our T S S except for the replacement of batteries which can be performed by quali...

Страница 41: ...ds from the output sockets After repeated overloads the UPS is locked in Bypass mode The connected loads are powered directly from the mains Disconnect the excess loads from the output sockets shut do...

Страница 42: ...he following fault codes 01 02 03 04 11 12 13 14 1A 21 24 35 36 41 42 or 43 are displayed on the LCD display and the audible alarm sounds continuously An internal fault has occurred in the UPS This is...

Страница 43: ...0 91 93 Performance at full load in ECO mode 95 96 97 99 Overload in line mode 110 130 5 min 100 110 2 min 130 140 30 sec 110 130 1 min 140 150 1 5 sec 130 1 sec 150 100 ms Overload in battery mode 11...

Страница 44: ...ill be 78 of the rated 6 As a frequency converter the power supplied will be 60 of the rated DSP Digital signal processor A DSP is a processor or microprocessor based system that has a set of instruct...

Страница 45: ...ing through the visible light spectrum to infrared the latter called IRED infra red emitting diode Circuit breaker A circuit breaker is a device capable of interrupting the electrical current of a cir...

Страница 46: ...46 SALICRU...

Страница 47: ...47 USER MANUAL...

Страница 48: ......

Отзывы: