Switching outputs
Switching behav‐
ior
PNP switching against supply voltage UV
OUT 1 ... OUT 3:
Resting level: High (no field breach), working level: Low (field breach)
Response time: 134 ms ... 30 s (configurable via SOPAS ET ), holding
time: 0 ms ... 10 s (configurable via SOPAS ET)
OUT 4:
Resting level: High (device ready),
working level: Low (error), low pulse (15 Hz, index, corresponds to mea‐
surement at 90°)
Properties
Short-circuit protected and temperature protected
Not electrically isolated from supply voltage U
v
Electrical values
0 V
≤
U
a
≤
U
V
(U
V
–1.5 V)
≤
U
a
≤
U
V
at I
a
≤
100 mA
Longer connecting cables at the switching outputs of the device should be avoided due
to the resulting fall in voltage. This is calculated as follows:
Δ
U = (2 x length x current) : (conductance value x cross-section)
Conductance value for copper: 56 m/
Ω
mm
2
.
Assignment of infringed fields - switching outputs
Fields of a field set
Switching outputs
OUT 1
OUT 2
OUT 3
Fields 1, 2, and 3 infringed
Active
Active
Active
Fields 2 and 3 infringed
Deactivated
Active
Active
Field 3 infringed
Deactivated Deactivated
Active
All fields free
Deactivated Deactivated Deactivated
Field 1: inner, field 2: center, field 3: outer
Active: in working position; deactivated: in resting position
Output level: The level of the switching outputs OUT 1 ... OUT 3 is active low (in resting
position: high, in working position: low (field infringed)).
All fields of a field set are also deemed to be infringed during switching on, booting, in
the event of an error, and when the device is switched off.
The OUT 4 switching output works with the following levels:
Function
Level
Device Ready
High
Index signal (15 Hz), corresponds to measure‐
ment at 90°
Low peaks
Fault
Low
3
PRODUCT DESCRIPTION
24
O P E R A T I N G I N S T R U C T I O N S | TiM781
8024231//2019-03-29 | SICK