Table 17: Number of monitoring cases
Application
Applications with local static control inputs on the S3000
4
Applications with static control inputs via EFI (e.g., on a
Flexi Soft)
32
Applications with dynamic control inputs via EFI
32
Complementary information
You can configure the monitoring cases in the CDS.
Each monitoring case includes the following information:
•
The input conditions, the so-called control signals that control the activation of the
monitoring case.
•
A field set comprising a protective field and warning field(s).
•
If necessary, a simultaneous field set.
•
If necessary, a unique follow-on case or two alternative follow-on cases.
•
The multiple sampling for the field set.
•
The multiple sampling for the simultaneous field set.
Monitoring cases can be switched with the following input information:
•
Static information
•
Speed information
•
A combination of the two
Further topics
•
7.12.1
Monitoring case switching via static input information
Overview
For monitoring case switching via static input information, you configure for each moni‐
toring case the input condition to be used to switch to this monitoring case.
Important information
WARNING
Persons or parts of the body to be protected may not be recognized or not recognized in
time in case of non-observance.
Someone may already be in the protective field at the time of switchover. Only by switch‐
ing in the correct time frame, i.e., before the hazard occurs at this point for the person,
is protection provided (
see "Timing for monitoring case switching", page 35
b
Make sure that the control – using static control inputs – provides switching
between the monitoring cases in the correct time frame.
NOTE
The control for the monitoring case switching must meet the required safety level.
The circuit for the control inputs must be suitable for the ambient conditions to be
expected so that systematic and design-related effects and resulting errors on the
switching of the monitoring cases can be excluded.
Static complementary sampling
Using the two control input pairs on the S3000 Cold Store, 2
2
= 4 monitoring cases can
be switched.
CONFIGURATION
7