Figure 52: Creating a field set in the CDS
Protective fields and warning fields can cover an angle of up to 190° and have different
radial scanning ranges depending on the sensor head and the resolution configured.
WARNING
Persons or parts of the body to be protected may not be recognized or not recognized in
time in case of non-observance.
Before commissioning the machine or vehicle, check the configuration of the protective
fields,
see "Checklist for initial commissioning and
.
b
Check the configured protective fields.
NOTE
3
or the warning fields
2
extend all the way to a wall or another
object (pillar, neighboring machine, shelf), there should be a distance of 100 mm
between the protective field or warning field and the object to prevent false triggering
1
.
7
CONFIGURATION
80
O P E R A T I N G I N S T R U C T I O N S | S3000 Cold Store
8012029/ZA20/2019-11-14 | SICK
Subject to change without notice