Full Integration and commissioning
8021386/12G4 /2019-04-24 | SICK
OPERATING INSTRUCTIONS | NAV-LOC
33
Subject to change without notice
The connectors (1), (5), (6), (7), (8), and (10) are not used for NAV-LOC and must remain unconnected.
The supply voltage is connected with male connector X2 to pin 3 (24 V In1) and 2 (GND).
Figure 11: X2 – Power connections (24V IN1 and 24V IN2 are designed with redundancy)
The X2-power indicators
10
light up if the connection is correct.
7.4
Network setup
7.4.1
SIM configuration
The SIM features 4 Ethernet interfaces. For each interface, an IP address is preconfigured. However, it
can be changed using the SOPAS ET software as described below.
The factory settings of the SIM2000-0A20A00 are shown in the following figure.
A PC can be connected to an Ethernet interface, for example to port X9-1, for setting the interface
configuration.
The interface of the PC must be set to an IP address in the range 192.168.0.2 – 192.168.255 in order
to reach the device using the interface with the IP address 192.168.0.1.
If necessary, the 4 Ethernet interfaces can be configured individually.
Logging into the device with the “Authorized Client” level with the password “client” is required.
10
LED 1 for power connection via X2:2 and X2:3, LED 2 for power connection via X2:5 and X2:6
192.168.0.1
192.168.1.1
192.168.2.1
192.168.3.1