11. Within the next 30 s, interrupt the protective field of the safety light curtain again
in the center until the COM LED flashes white once (after about 3 s).
12. Stop the interruption within the next 30 s.
✓
The run direction of LEDs 1 to 5 (
Ö
blue) points outwards; it points to the next
interruption.
13. Keep the protective field of the safety light curtain clear until the COM LED flashes
white once (after about 3 s).
14. Within the next 30 s, interrupt the protective field of the safety light curtain exter‐
nally until the COM LED flashes white once (after about 3 s).
15. Stop the interruption within the next 30 s.
16. Keep the protective field of the safety light curtain clear until the COM LED flashes
white and LEDs 1 to 5 flash blue three times (after about 3 s).
17. Switch off the safety light curtain within the following 2 min.
✓
EDM or reset is deactivated at the next switch-on.
18. After deactivating the configuration, check the wiring and adjust it to the desired
function if necessary.
19. If EDM or reset must be reactivated after deactivating the configuration, the
desired configuration must be repeated.
20. Check the effectiveness of the protective device.
Further topics
•
•
"Configuring external device monitoring (EDM)", page 65
•
7.4
Cascading
Overview
A maximum of 3 safety light curtains can be connected into a cascaded system.
7
CONFIGURATION
68
O P E R A T I N G I N S T R U C T I O N S | miniTwin4
8012624/10OM/2018-08-09 | SICK
Subject to change without notice