28
8011952/YWL2/3-0/2016-08| SICK
O P E R A T I N G I N S T R U C T I O N S | DUSTHUNTER C200
Subject to change without notice
2
PRODUCT DESCRIPTION
2
I/O module
Apart from the standard analog output, the DUSTHUNTER C200 has an Analog module with
two outputs 0/4 ... 22 mA (max. load 500
Ω
) integrated to output further measured vari-
ables. The module is plugged onto a module carrier connected to the processor board with
a special line.
Options
1
1x analog input module with two inputs 0/4 ... 22 mA (
) to read-in values from external sensors (gas temperature, internal duct
pressure, moisture, O
2
) to calculate the dust concentration in standard state.
An additional module carrier docked to the existing ones is required for this option.
2
Module to pass on measured values, system status and service information to higher
level control systems, optionally for Profibus DP V0, Modbus TCP or Ethernet (type 1 or
type 2), to plug onto a hat rail (
see “Options for MCU control unit”, page 123
A corresponding line serves to connect the module to the processor board.
3
MCU remote control unit
The MCU remote control unit has identical functions to the MCU display near the device,
however, it can be installed further away.
– Operating function the same as the MCU display
– Distance to the device:
- MCU remote control unit without separate power supply unit: Max. 100 m
- MCU remote control unit with own power supply unit: Max. 1000 m
– The MCU and the MCU remote control unit are interlocked (it is not possible to
operate both MCUs at the same time).
Profibus DP-V0 for transfer via RS485 according to DIN 19245 Part 3 as well as
IEC 61158.