Aqua Timer Plus

 - 

                                                                                                                                      

20/34 

 

 

 

6.2.6 – LLL2 – LL–3 – One duplex column with mixed time / volume start. 

 

6.2.6.a – Operative characteristics. 

 

In this operative modality the control for the start of the regeneration depends on the use or otherwise of the cam with 

stand-by, that is of the programming of the flags 

1CL

 and 

2CL

 

If both of the flags are programmed with the value 

0

, the regeneration cycle is standard in 4 phases of 25 seconds. The 

start of the cycle is controlled by the running out of the interval time between two regenerations, or by the running out 

of  the  volume.  The  latter  condition,  differently  from  that  described  in  par.  6.2.3.a,  does  not  activate  a  request  for 

regeneration to be carried out at the programmed time, but causes the immediate start

 

of the cycle. 

 

The same effect is obtained also by programming to 

1

 only the flag 

2CL

, that is when the standard regeneration cycle 

standard with a stand-by cam is required to be carried out. 

 

If both of the flags are programmed with the value 

1

, the controller carries out the regeneration with stand-by. In this 

case, the running out of the volume causes a request for regeneration which will be carried out at the programmed time. 

The controller will immediately position the cam in the stand-by position, that is it will carry out the exchange of the 

columns. The regeneration will start from the stand-by position.  

 

The control on the 

reserve

 is not available.  

The control on the 

remote start 

is available, and this can start up the regeneration both immediately and deferred to the 

programmed time, on the basis of the content of the flag 

2HL

 

 

6.2.6.b – Programming of the FLAGs 

 

Tab. 20 is to be used for the programming of the flags for the modality 

LLL2 – LL-3  

 

Tab. 20 – Selection of the operative modality duplex column - start in mixed mode  

 

FLAG 

Display

 

Operative state / Data visualised 

Program 

 

S C - -

 

State of access to the selection of the programming codes 

Advance

 

 

S C 0 9

 

With the key 

Advance

 the programming code is increased up to 9 

Program 

 

L L L 2

 

Duplex column modality. If necessary modify the data with 

Advance 

 

Program 

 

L L - 3

 

Mixed regeneration. If necessary modify the data with 

Advance

Program 

0 H L

 

0 H L 0

 

FLAG not used 

Program 

1 H L

 

1 H L 0

 

Interval between two regenerations expressed in days. 

See par. 6.3.2

 

Advance 

1 H L

 

1 H L 1

 

Regeneration to be carried out on the days of the week programmed. 

Program 

2 H L

 

2 H L 0

 

Immediate start of the regeneration at the command of the remote start. 

See par. 6.5 

Advance 

2 H L

 

2 H L 1

 

Start of the regeneration at the programmed time on the command of the remote 

start 

Содержание Aqua Timer Plus

Страница 1: ...1 34 USE AND MAINTENANCE MANUAL AQUA TIMER PLUS y Distributed b 37 Tannery Lane 06 08 Tannery House Singapore 347790 Tel 65 6741 2994 Fax 65 6741 2995 S I A T A Asia Pacific Pte Ltd Distributed by ww...

Страница 2: ...oltage 73 23 CEE 93 68 CEE The fulfilment of the following regulations has been verified EN 50081 1 General Regulation on Emissions part 1 residential commercial and light industry environment EN 5008...

Страница 3: ...volume start 20 6 3 PROGRAMMING CODES 22 6 3 1 Access to the programming codes 22 6 3 2 List of programming codes and their meaning 22 6 4 PROGRAMMING OF THE RESERVE 23 6 5 REMOTE START 24 6 6 PROGRAM...

Страница 4: ...ion in progress or to jump one or more phases by pressing the key Regener during the stop phase Aqua Timer Plus makes it possible to use an outlet which is activated during the second phase of the reg...

Страница 5: ...10 Network frequency 50 Hz 3 Power absorbed 30 VA Operative temperature 0 C 55 C Class of protection IP65 Protection from disturbances ICE 65 Trial class 4 3000 V Reading scale 0 999 999 Litri Box di...

Страница 6: ...on mixed control time volume for the regen Tab 2 Functionality of the keys Key Description CODE Access to the programming of the work parameters through the protection code During the programming retu...

Страница 7: ...box with a label identifying the product carrying the following infrormation name of producer and PN producer AT PLUS2 05 the quick reference guide for the installation and programming may be found in...

Страница 8: ...h free contact outlets with the following signals Dosing pump End of cycle impulse Impulse during phase 2 Alarm Regeneration in progress Warning Before carrying out any installation and or maintenance...

Страница 9: ...ing the service The programming will be carried out via the keypad on the front of the controller Aqua Timer Plus has the following operative modalities Tab 4 Table of the operative modalities Code De...

Страница 10: ...Code 0 0 0 0 Key in the protection code programmed with the function SC07 Advance 0 0 0 2 Key the code on the display with the keys Advance and Code Code S C State of access to the keying in of the p...

Страница 11: ...0 9 By pressing Advance key the programming code is increased up to 9 Program L L L 1 Single column modality If necessary modify the data with Advance Program L L 1 Regeneration by time If necessary m...

Страница 12: ...eps programming SC05 End of cycle impulse duration and dosing pump divider programming SC00 Initialisation of the system 6 2 2 LLL1 LL 2 One single column with start by volume 6 2 2 a Operative charac...

Страница 13: ...FLAG not used Program 2 H L 2 H L 0 Immediate start of the regeneration at the command of the remote start See par 6 5 Advance 2 H L 2 H L 1 Start of the regeneration at the time programmed at the com...

Страница 14: ...the regeneration cycle stop times SC04 Programming of the litre counter divider prescaler SC05 Programming of the duration of the end of cycle impulse and of the litre counter divider of the dosing pu...

Страница 15: ...days of the week programmed Program 2 H L 2 H L 0 Immediate start of the regeneration at the command of the remote start See par 6 5 Advance 2 H L 2 H L 1 Start of the regeneration at the programmed...

Страница 16: ...on the volume or on the reserve Control is available on the remote start which can start up the regeneration both immediately and deferred to the programmed time on the basis of the content of the fl...

Страница 17: ...Management of the start of the regeneration in the case of inhibit See par 6 12 Program 1 d L 1 d L 0 FLAG not used Program 2 d L 2 d L 0 FLAG not used Program 3 d L 3 d L 0 FLAG not used Program Fast...

Страница 18: ...rt by volume FLAG Display Operative state Data visualised Program S C State access to the selection of the programming codes Advance S C 0 9 With the key Advance the programming code is increased up t...

Страница 19: ...unter divider prescaler SC05 Programming of the duration of the end of cycle impulse and of the litre counter divider of the dosing pump SC06 Programming of the volume of resin of the percentage of re...

Страница 20: ...controller will immediately position the cam in the stand by position that is it will carry out the exchange of the columns The regeneration will start from the stand by position The control on the re...

Страница 21: ...not used Program 2 d L 2 d L 0 FLAG not used Program 3 d L 3 d L 0 FLAG not used Program Fast flashing of the display The programming is memorised in eeprom 6 2 6 c List of codes to be programmed For...

Страница 22: ...visualises the new value Causes any regeneration in progress to end immediately S C 0 1 PROGRAM d H x x Programming of the hardness value of the water from 1 to 99 The hardness value must be expresse...

Страница 23: ...9 0 S C 0 7 PROGRAM x x x x Programming of the code of access to the programming functions Using the key Advance any value from 0 to 9999 may be set S C 0 8 PROGRAM x x x x Allows the total counter of...

Страница 24: ...atio between the number of impulses read by Aqua Timer Plus and the unit of load in transit in the counter used litres or m Aqua Timer Plus has two work modes free prescaler if the flag 0CP is equal t...

Страница 25: ...ed prescaler the volume calculated is optimised by returning to zero the digits which are not decreased and by rounding it off Example If the volume calculated is 15 435 litres and the prescaler is pr...

Страница 26: ...rotation time of the first phase must therefore be of 50 seconds 25 dedicated to reaching the position of stand by and 25 to reach the position expected for the first phase The movement time between...

Страница 27: ...Time diagram of the standard regeneration cycle and cam with stand by Type 2 Pos of stand by 1C 2C 3C 4C Search of the stroke end Stop Stop Stop Stop Stroke end Stroke end Movement phase of 25 second...

Страница 28: ...unters and turn off the led SALT When the number of regenerations which can be carried out reaches the value dd00 one last regeneration is available after which Aqua Timer Plus is blocked with the led...

Страница 29: ...f the columns The connections shown in the table must be respected rigorously to avoid damaging the sensor In the second case there are only two wires between which there is a closure for each impulse...

Страница 30: ...e clock has passed the time programmed for the start of the cycle the regeneration will not be able to start until the conditions are repeated that is after 24 hours To avoid waiting for 24 hours with...

Страница 31: ...ua Timer Plus at 230 Vac AT PLUS2 05 this fuse must be of delayed 0 5A 7 2 the motors of the distributors do not stop 1 Check that the run end wires of the distributors marked 96 S are correctly inser...

Страница 32: ...Aqua Timer Plus 32 34 Appendix A General electrical connections CE0027...

Страница 33: ...Aqua Timer Plus 33 34 Appendix B Electrical connections for the single distributor CE0028...

Страница 34: ...dix C Electrical connections for the duplex distributor CE0021 Distributed by 37 Tannery Lane 06 08 Tannery House Singapore 347790 Tel 65 6741 2994 Fax 65 6741 2995 S I A T A Asia Pacific Pte Ltd Dist...

Отзывы: