6.2.1 – LLL1 – LL–1 – One single column with start by time
6.2.1.a – Operative characteristics
.
In this operative modality, the regeneration starts exclusively at the programmed time, after the interval days
programmed (or on the days of the week selected).
No control on the volume or on the reserve is available.
Control on the
remote start
is available, which can start up the regeneration both immediately or deferred to the
programmed time based on the content of the flag
2HL
.
In this operative modality it is not possible to activate the cycle with the
stand-by
.
6.2.1.b – FLAG Programming
The tab. 8 is to be used in the programming of the flag for the modality
LLL1 – LL–1
Tab. 8 – Selection of the operative modality single column - time start
FLAG
Display
Operative state / Data visualised
Program
S C - -
State of access to the selection of the programming codes
Advance
S C 0 9
By pressing
Advance
key the programming code is increased up to 9
Program
L L L 1
Single column modality. If necessary modify the data with
Advance
Program
L L - 1
Regeneration by time. If necessary, modify the data with
Advance
.
Program
0 H L
0 H L 0
FLAG not used
Program
1 H L
1 H L 0
Interval between two regenerations expressed in days.
See par. 6.3.2
Advance
1 H L
1 H L 1
Regeneration to be carried out on the days of the week programmed.
Program
2 H L
2 H L 0
Immediate start up of the regeneration on the command of the remote start.
See par. 6.5
Advance
2 H L
2 H L 1
Start of the regeneration at the programmed time at the command of the remote
start
Program
3 H L
3 H L 0
FLAG not used.
Leave programmed at 0
Program
0 C L
0 C L 0
Modality of the litre counter divider.
Do not use
.
see par. 6.6
Program
1 C L
1 C L 0
FLAG not used.
Leave programmed at 0
Program
2 C L
2 C L 0
FLAG not used.
Leave programmed at 0
Program
3 C L
3 C L 0
Management of salt alarm
disabled
Advance
3 C L
3 C L 1
Management of salt alarm
enabled. See par. 6.9
Program
0 d L
0 d L 0
Normal functioning