6.2.2.c – List of codes to be programmed
For the programming and the meaning of the codes see par. 6.3. In this modality the programming of the following
codes is recommended:
Tab. 11 – Table of the codes in one single column modality LLL1 – LL–2
Code
Meaning
SC03
Programming of the regeneration cycle ( stop times )
SC04
Programming of the litre counter divider ( pre-scaler )
SC05
Programming of the duration of the end of cycle impulse and of the litre counter divider of the
dosing pump
SC06
Programming of the volume of resin, of the percentage of reserve and of the capacity of exchange
SC01
Programming of the hardness value
SC00
Initialisation of the system
If the flag
0HL
has been programmed with the value
1
to also have the regeneration by time, the programming
recommended varies as follows:
Tab. 12 – Table of the codes in one single column modality LLL1 – LL–2
Code
Meaning
SC02
Programming of the time of regeneration and the interval days between two regenerations
SC03
Programming of the regeneration cycle ( stop times )
SC04
Programming of the litre counter divider ( prescaler )
SC05
Programming of the duration of the end of cycle impulse and of the litre counter divider of the
dosing pump
SC06
Programming of the volume of resin, of the percentage of reserve and of the capacity of exchange
SC01
Programming of the hardness value
SC00
Initialisation of the system
6.2.3 - LLL1 – LL–3 – One single column with mixed time / volume start.
6.2.3.a –Operative characteristics.
In this operative modality, the regeneration starts exclusively when the
interval days
have passed and at the
programmed time.
If the volume of water treated reaches the value calculated for the
reserve,
the residual days will be
ignored
. It is not possible to have the immediate start of the regeneration either because the volume has run out, or
because the value of the reserve has been reached. The control on the reserve is
automatic and cannot be dis-
activated.
The control on the
remote start
is available, and can start up the regeneration both immediately and deferred to the
programmed time, based on the content of the flag
2HL
.
In this operative modality the possibility of using the cam with the
stand-by
is not available.