75
12.6 ORP Input Group
Character
Setting Item, Setting Range
Factory Default
Data
Moving average data amount
3
1 to 20
Input high limit
2000 mV
Input low limit to 2000 mV
Input low limit
-2000 mV
-2000 mV to Input high limit
ORP input filter time constant
0.0 sec.
0.0 to 60.0 sec.
12.7 EVT1 Action Group
Character
Setting Item, Setting Range
Factory Default
Data
EVT1 type
No action
: No action
: ORP input low limit action
: ORP input high limit action
: Cleansing output
: ORP input error alarm output
EVT1 value
0 mV
Input low limit to Input high limit
EVT1 proportional band
0 mV
0 to 4000 mV
EVT1 reset
0 mV
200 mV
EVT1 hysteresis type
Reference Value
: Medium Value
: Reference Value
EVT1 ON side
10 mV
0 to 200 mV
EVT1 OFF side
10 mV
0 to 200 mV
EVT1 ON delay time
0 sec.
0 to 10000 sec.
EVT1 OFF delay time
0 sec.
0 to 10000 sec.
EVT1 proportional cycle
30 sec.
1 to 300 sec.
EVT1 output high limit
100%
EVT1 output low limit to 100%
EVT1 output low limit
0%
0% to EVT1 output high limit