26
Character
Setting Item, Function, Setting Range
Factory Default
Output OFF time when EVT1 output ON
0 sec.
• Sets Output OFF time when EVT1 output is ON.
If ON time and OFF time are set, EVT1 output can be turned ON/OFF
in a configured cycle when EVT1 output is turned ON.(Fig. 7.3-2, p.28)
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT1 type].
• Not available for P control action
• Setting range: 0 to 10000 sec.
EVT1 ORP input error alarm EVT
type
No action
• Selects EVT
output type (except EVT1 type) in order to assess
EVT1 ORP input error alarm.
• Available only when
(ORP input error alarm output) is
selected in [EVT1 type]
•
: No action
: EVT2 action
: EVT3 action
: EVT4 action
EVT1 ORP input error alarm span
when EVT
output ON
0 mV
• Sets span to assess EVT1 ORP input error alarm when EVT
output
(selected in [EVT1 ORP input error alarm EVT
type]) is ON.
• Available only when
(ORP input error alarm output) is
selected in [EVT1 type]
• Setting range: 0 to 2000 mV
When set to 0 (zero), ORP input error alarm is disabled.
EVT1 ORP input error alarm time
when EVT
output ON
0 sec.
• Sets time to assess EVT1 ORP input error alarm when EVT
output
(selected in [EVT1 ORP input error alarm EVT
type]) is ON.
• Available only when
(ORP input error alarm output) is
selected in [EVT1 type]
• Setting range: 0 to 10000 seconds or minutes
(*)
When set to 0 (zero), ORP input error alarm is disabled.
(*) Time unit follows the selection in [ORP input error alarm time unit].