73
11.2 Key Operation
Problem
Possible Cause
Solution
Unable to set values.
The values do not
change by the
or
key.
(Lock 1) is selected
in [Set value lock (p.47)].
(The LOCK indicator is lit when
Lock 1 is selected.)
Select
(Unlock).
Only EVT1 to EVT4
values can be set.
Other settings are
impossible.
The values do not
change by
or
key.
(Lock 2) is selected
In [Set value lock (p.47)].
(The LOCK indicator is lit when
Lock 2 is selected.)
Select
(Unlock).
Unable to enter
Manual Cleansing
Mode.
(Cleansing output) is
not selected in any of [EVT1
type to EVT4 type (pp. 23, 29,
35, 41)].
Select
(Cleansing
output) in any of [EVT1 type
to EVT4 type (pp. 23, 29, 35,
41)].
Cleansing action is performing
using the ‘Cleansing Time’ and
‘Restore Time after Cleansing’
settings.
Execute Manual cleansing
after cleansing action is
complete.
Unable to enter a
calibration mode
(Adjustment mode or
Span sensitivity
correction mode).
(Lock 1),
(Lock 2) or
(Lock 3)
has been selected in [Set
value lock (p.47)].
(The LOCK indicator is lit when
Lock 1, Lock 2 or Lock 3 is
selected.)
Select
(Unlock).
(Cleansing output)
has been selected in any of
[EVT1 type to EVT4 type (pp.
23, 29, 35, 41)], and cleansing
action is performing using the
‘Cleansing Time’ and ‘Restore
Time after Cleansing’ settings.
Perform calibration after
cleansing action is complete.