7.3 EVT1 Action Group
To enter the EVT1 Action group, follow the procedure below.
1
Press the
key twice in ORP Display mode or Cleansing
Output mode.
2
Press the
key.
The unit proceeds to the EVT1 Action group, and ”EVT1 type“ will appear.
Character
Setting Item, Function, Setting Range
Factory Default
EVT1 type
No action
• Selects an EVT1 output (Contact output 1) type. (Fig 7.3-1, p.28)
Note: If EVT1 type is changed, EVT1 value defaults to 0.
•
: No action
: ORP input low limit action
: ORP input high limit action
: Cleansing output
: ORP input error alarm output
EVT1 value
0 mV
• Sets EVT1 value. (Fig 7.3-1, p.28)
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT1 type].
• Setting range: Input low limit to Input high limit
EVT1 proportional band
0 mV
• Sets EVT1 proportional band. (Fig 7.3-1, p.28)
ON/OFF control action when set to 0.
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT1 type].
• Setting range: 0 to 4000 mV
EVT1 reset
0 mV
• Sets EVT1 reset value.
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT1 type].
• Not available for the ON/OFF control action.
• Setting range:
200 mV