10
3. Mounting to the Control Panel
3.1 Site Selection
Caution
Use within the following temperature and humidity ranges:
Temperature: 0 to 50
(32 to 122
) (No icing)
Humidity: 35 to 85 %RH (Non-condensing)
If AER-101-ORP is mounted through the face of a control panel, the ambient
temperature of the unit – not the ambient temperature of the control panel – must
be kept to under 50 , otherwise the life of electronic parts (especially electrolytic
capacitors) of the unit will be shortened.
This instrument is intended to be used under the following environmental
conditions (IEC61010-1): Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions:
• A minimum of dust, and an absence of corrosive gases
• No flammable, explosive gases
• No mechanical vibrations or shocks
• No exposure to direct sunlight, an ambient temperature of 0 to 50
(32 to 122 )
that does not change rapidly
• An ambient non-condensing humidity of 35 to 85 %RH
• No large capacity electromagnetic switches or cables through which large current
is flowing
• No water, oil or chemicals or where the vapors of these substances can come into
direct contact with the unit
3.2 External Dimensions (Scale: mm)
(Fig. 3.2-1)
11.5
104.5 (when terminal cover is used)
98.5
10
6.
2
91
Gasket
Screw type mounting bracket
Terminal cover (sold separately)
48
96