10 

(1)  WATER TEMP (Coolant Temperature) Warning Indicator (High Water Temp.) 

 

 

  CAUTION: BURNS

 

 

 Do not open the radiator cap immediately after stopping the engine. 

Do so will result in hot steam gushing out. 

 Hot steam gushes out from the coolant sub-tank if the generator overheats. 

Do not touch the coolant sub-tank. 

 

 

If the coolant temperature rises above 230 °F durin g operation, the WATER TEMP and 
ENGINE warning indicators light up, and the engine automatically stops. If this occurs, hot 
steam will gush out of the coolant sub-tank. Check the coolant sub-tank coolant level after 
the generator cools and add coolant to the coolant sub-tank if it is insufficient. (Refer to 
section “8-2. Checking Coolant”.) If the coolant is at the specified amount, it is probable 
that the fan belt is loose or there is a coolant leak. Wait for the engine to cool and inspect for 
these problems. 

< NOTE > 

 The coolant temperature cannot be detected if the coolant level is excessively low. Always be 

sure to check the coolant level in the radiator coolant sub-tank before starting work. 

 

(2)  OIL PRESS (engine oil pressure) Warning Indicator (Low Oil Press.) 

 

 

  CAUTION: BURNS

 

 

 Always be sure to stop the engine and allow the engine to cool when 

performing inspection or maintenance of engine oil. Opening the oil gauge or 
oil filler cap during operation will result in hot oil gushing out. 

 

 

If the engine oil pressure drops below 7 psi (0.49 x 100 kPa) during operation, the OIL 
PRESS and ENGINE warning indicators light up, and the engine automatically stops. If this 
occurs, check the engine oil level and add engine oil until it reaches the maximum level. 

< NOTE > 

 This oil pressure warning indicator cannot detect oil deterioration. Change the engine oil 

periodically. (Refer to section “8-1. Checking Engine Oil”.) 

 

(3)  OVER SPEED (Engine Overspeed) Warning Indicator 

This generator is equipped with a function such that the engine is automatically stopped if an 
engine fault occurs causing the engine speed to increase excessively. If the engine speed 
rises above 2070 rpm during operation, the OVER SPEED and ENGINE warning indicators 
light up, and the engine automatically stops. If this occurs, it is probable that some 
malfunction has occurred in the engine. Contact the authorized distributor where the 
generator was purchased. 

 

(4)  BATTERY (Battery Charge) Warning Indicator (Low Battery Voltage) 

The BATTERY warning indicator lights up when charging is not possible during operation. If 
charging is not possible and the battery voltage drops below 8 V, the ENGINE warning 
indicator also lights up and the engine automatically stops. If this occurs, contact the 
authorized distributor where the generator was purchased. 

< NOTE > 

 This battery charging warning indicator cannot detect battery deterioration or insufficient battery 

fluid. (Refer to section “8-7. Checking the Battery”.) 

Содержание DGM60MK

Страница 1: ...ertical Water Cooled 4 Cycle Diesel Engine DGM60MK LU X750 020 73 0 X750801 370 0 CAUTION Do not operate the Generator or any other appliance before you have read and understood the instructions for u...

Страница 2: ......

Страница 3: ...ration Store this manual in a specified location where it will be secure and available for consulting at any time Order another copy from the authorized distributor where this generator was purchased...

Страница 4: ...1 Load Cable Selection 17 7 2 Connecting Load Cables 18 8 Pre Operation Inspection 21 8 1 Checking Engine Oil 21 8 2 Checking Coolant 22 8 3 Checking the Fan Belt 23 8 4 Checking the Fuel 23 8 5 Chec...

Страница 5: ...y when performing inspection or maintenance Do not suspend using tie downs Use of such could result in the generator falling Do not lift any additional weight such as fuel tanks or trailers No persons...

Страница 6: ...ys be sure to stop the engine and allow the engine to cool when performing inspection or maintenance of engine oil Opening the oil gauge or oil filler cap during operation will result in hot oil gushi...

Страница 7: ...enthesis Injury Part no X505 004630 Simul Phase Part no X505 006960 Caution gm spec LLC Part no X505 004650 Caution fire Part no X505 004880 Caution do not change Part no X505 004620 Injury Part no X5...

Страница 8: ...ta V3800DI TI No of Cylinders bore stroke in mm 4 3 94 4 72 100 120 Continuous Rated Output hp 77 Rated Speed rpm 1800 Displacement Cu in liters 230 3 769 Combustion System Direct Injection Turbo char...

Страница 9: ...nt temperature 5 to 104 F 15 to 40 C Relative humidity 80 or less Elevation 984 ft 300 m or less 3 Applications Power source for submerged pumps and similar civil engineering equipment Power source fo...

Страница 10: ...eck Door Air Cleaner Coolant Sub Tank Engine Check Door Fuel Pre Filter External Tank Fuel Inlet External Tank Fuel Return Oil Drain plug Coolant Drain plug 3way fuel valve Radiator Plate Radiator Tie...

Страница 11: ...e Speed Selector Switch Volt eter 13 Display Selector Switch Am eter 14 Available Output Monitor Frequency Meter 15 Fuel Meter Pilot Lamp 16 Hour Meter Voltage Regulator 17 Pre Heating Indicator Ammet...

Страница 12: ...ans that usage has exceeded the rated capacity Immediately stop the equipment being used and reduce the load capacity of the equipment 5 2 Warning Indicators This generator is equipped with the follow...

Страница 13: ...on will result in hot oil gushing out If the engine oil pressure drops below 7 psi 0 49 x 100 kPa during operation the OIL PRESS and ENGINE warning indicators light up and the engine automatically sto...

Страница 14: ...uthorized distributor where the generator was purchased 5 3 Meters and Gauges Engine Meters and Gauges 1 Hour Meter Displays the operating time Use this as a rough estimate for managing the timing of...

Страница 15: ...ltage meter value 2 Ammeter Displays the output current phase current of the generator Turn the ammeter selector switch to L1 U to display the output current of the three phase L1 phase and single pha...

Страница 16: ...r selecting the tripping order of the three phase and single phase breaker when there is a short circuit or overload on the load side If the three phase or single phase breaker is selected for precede...

Страница 17: ...e generator is equipped with the following in order to prevent liquid from spilling in case you forget to flush the liquid The operation panel is equipped with an indicator that lights up when its sen...

Страница 18: ...e generator internal parts and the external fuel ports 6 Transporting Installing 6 1 Transport Procedures WARNING INJURY Do not suspend using tie downs Use of such could result in the generator fallin...

Страница 19: ...ion area and take measures to prevent persons not involved in the construction from entering the area Position this generator on a hard flat and level surface that serves as the foundation Position th...

Страница 20: ...e from the generator to the equipment using the generator NOTE Select cable with a thickness that ensures that the voltage drop across the cable will be within 5 of the rated voltage Load Cable Select...

Страница 21: ...power source are all matching If using the N G terminal be careful that the currents of each phase are uniform If using three phase output simultaneously with a single phase three wire type output use...

Страница 22: ...oad U W terminal voltage is 240 V U N G terminal voltage is 120 V W N G terminal voltage is 120 V For single phase 240 V load For single phase 120 V load Single phase 120 V receptacle single phase 240...

Страница 23: ...erminals U N G and W N G connect an equivalent load between U N G and W N G If using a single phase three wire output terminal simultaneously with a receptacle output make sure that currents passing t...

Страница 24: ...o that no oil remains and then re insert the dipstick fully Prior to starting the engine make sure to fill the engine oil through the oil filler so that it reaches the MAX line NOTE Wait approximately...

Страница 25: ...hten the radiator cap Attach the radiator plate NOTE Use a 50 50 mix of Long Life Coolant LLC for engine coolant Use GM SPEC 6277M or equivalent Always use potable water when mixing the coolant Use LL...

Страница 26: ...hten the alternator installation bolts and nuts two locations Check that the fan belt tension is correct 4 Replacing the Fan Belt Request the authorized distributor where the generator was purchased t...

Страница 27: ...before operating Open the check door and check the inside of the spill containment Flush out any accumulated liquid Refer to section 10 Inspection Maintenance 8 Flushing Liquid in Spill Containment fo...

Страница 28: ...ck the fluid level and add distilled water when it is near the lower level until it reaches the upper level Check the terminals for looseness and tighten if loose NOTE It is necessary to recharge the...

Страница 29: ...1 m or more from walls or other hindrances and on a level surface CAUTION NJURY Do not operate the generator if it has been modified or any parts have been removed Position the generator on a level s...

Страница 30: ...ection and load power source are consistent Turn the three phase and single phase breakers on the operation panel to OFF and stop operation Turn the lever of the voltage selector switch to the desired...

Страница 31: ...h an automatic air bleeding mechanism Perform the following procedures when the engine stops due to running out of fuel to easily bleed the air from the system Add fuel to the generator Turn the start...

Страница 32: ...stopped or an indicator lamp lights up to stop the engine Protection Feature List No Action Abnormality Breaker Trip Engine Automatic Shutdown Warning Lamp Flash Cause 1 High Water Temperature Activa...

Страница 33: ...m 0 to 10 ft 3 m from the underside of this generator The fuel level of the external fuel tank being lower than this generator will result in poor engine operation or stoppage Turn the 3way fuel valve...

Страница 34: ...s Always be sure to use lifting hooks when suspending the generator and raise it slowly at a completely vertical angle Perform periodic inspection and maintenance according to the following table in o...

Страница 35: ...ents Drain Main Pre fuel filter Replace Replace Fuel tank Drain water Water separator and Gauze filter Clean Clean Fuel tank Clean Check for leaks Fuel Oil Coolant Fuel hose Replace Air cleaner elemen...

Страница 36: ...00 hours Drain the engine oil Refer to section 1 Engine Oil Replacement Remove the oil filter using a filter wrench Spread a thin layer of oil on a new oil filter gasket Thread the oil filter by hand...

Страница 37: ...ow compressed air from inside the element If carbon or oil is adhering Replace with new parts 4 Draining Water from the Water Separator Check Daily Clean Every 200 hours Drain water when the float red...

Страница 38: ...d reinsert the fuel drain plug with new packing with rubber seal NOTE Replace the packing of the fuel drain plug with new packing each time the water is drained Packing part no V106 000110 After reins...

Страница 39: ...e plug hold the drain valve fixed using a spanner or similar tool and turn the plug If oil or other liquid is mixed in with the flushed liquid this indicates that there is an oil leak In such case che...

Страница 40: ...inment reassemble the spill container with this generator by performing the above procedures in the reverse order Reassemble the fuel piping and wiring connector to their original positions NOTE After...

Страница 41: ...38 Lifting Hook Wire Connector Bolt Spill Containment Fuel Line Inlet Side Fuel Line Return Side Wire Connector Bolt Fuel Tank Male Screw Nut Union Joint...

Страница 42: ...Allow the generator to cool before covering with the protective cover CAUTION BURNS Do not touch the engine and surrounding components immediately after stopping the engine as they are still hot 1 Sto...

Страница 43: ...of withstanding the double stacking weight Always be sure to use lifting hooks when suspending this generator Insert wood ties of the same size and that are wider than this generator between each gene...

Страница 44: ...uel line is frozen 3 Pre heater is defective 1 Use winterized fuel 2 Drain water in fuel line 3 Ask our distributor to repair Engine starts but stalls immediately 1 Fuel filter is clogged 2 Gauze filt...

Страница 45: ...ter is defective 2 AVR is defective 3 Voltage regulator dial is defective 1 Ask our distributor to repair 2 Ask our distributor to repair 3 Ask our distributor to repair Pointer exceeds the rated volt...

Страница 46: ...43 13 Generator Circuit Diagram...

Страница 47: ...44 14 Engine Electrical Circuit Diagram...

Страница 48: ...2011...

Отзывы: