37
(9) Spill Containment Cleaning/Inspection
WARNING : INJURY
Do not use the fuel tank lifting hook to suspend a gas tank that contains fuel,
and do not suspend with the fuel tank and spill containment as a single unit.
Doing so could result in the tank falling.
Clean
Every 500 hours
Separate the spill containment from this generator to clean and inspect the spill containment.
Separate the spill containment according to the following procedures.
Remove the wiring connector.
Remove the fuel piping (supply and return sides) (union joint).
Remove the four spill containment fixing bolts (M16).
< NOTE >
If removing the union joint from the connection, grasp both the screw and nut with spanners to
remove them.
Prepare a container to receive the fuel remaining in the fuel piping that will flow out of the
removed fuel piping.
Lift the generator, separate the spill containment and set the generator on a flat surface.
After cleaning and inspecting the inside of the spill containment, reassemble the spill
container with this generator by performing the above procedures in the reverse order.
Reassemble the fuel piping and wiring connector to their original positions.
< NOTE >
After reassembling, bleed air from the fuel system.
(Refer to section “9-3. Procedures during Operation”.)
After reassembling, check that there is no fuel leakage.
Spill Containment Cleaning/Inspection
Use a high-pressure cleaner or similar equipment to clean the inside of the spill
containment.
Remove the drain plug (R1) to drain the cleaning water.
After cleaning, allow water to accumulate and check that the spill containment has no
internal leakage.
Next, check that there no rust has developed inside of the spill containment. If rust has
developed, remove the rust and clean again.
After the procedures have been completed, apply sealant coating to the plug (R1) or
wrap it in seal tape.
< NOTE >
If the fluid drained when cleaning the spill containment contains oil
or grease, dispose of it according to the related laws and
regulations.
If the spill containment has a leak, contact the authorized distributor
where the generator was purchased.
4
1
Drain Plug (R1)
1
2
3
5
6
2
3
4
5