(5) AIR FILTER (Air Cleaner Clogging) Warning Indicator
The AIR FILTER warning indicator lights up if the air cleaner element becomes clogged
during operation. If it lights up, immediately stop the engine and clean or replace the air
cleaner element.
(Refer to section “10. Inspection/Maintenance (3) Air Filter Element Cleaning/
Replacement”.)
(6) SPILL CONTAINMENT (Spill Containment Amount) Warning Indicator
The SPILL CONT warning indicator lights up if the liquid stored in the spill containment
exceeds approximately 10 gal. during operation. If it lights up, immediately stop the engine
and flush the liquid stored in the spill containment.
(Refer to section “10. Inspection/Maintenance (8) Flushing Liquid in Spill Containment”.)
(7) ENGINE (Engine Malfunction) Warning Indicator
The ENGINE warning indicator lights up if the coolant temperature is high, the oil pressure is
low, the engine overspeeds, the battery voltage is low or some other engine fault occurs
during operation. If this occurs, a malfunction code is displayed on the engine and available
output monitors, and the engine automatically stops or the engine output is reduced.
If the ENGINE warning indicator lights up, contact the authorized distributor where the
generator was purchased.
5-3. Meters and Gauges
Engine Meters and Gauges
(1) Hour Meter
Displays the operating time. Use this as a rough estimate for managing the timing of periodic
inspection. Be careful as the hour meter operates when the starter switch is at RUN
regardless of whether the engine is running.
(2) Engine Monitor
Displays the engine speed, water temperature and oil
pressure. Switching the selector switch changes the
display in the following order: Speed
→
Water temp
→
Oil
press. Engine speed is first displayed when the engine is
started.
Speed
Displays the engine speed. 1800 rpm is displayed
when at 60 Hz.
Water Temp
Displays the temperature of the engine coolant.
Normal temperature displayed during operation should generally between 158 and
203 °F depending on use conditions.
< NOTE >
If the coolant temperature rises above 212 °F, imm ediately stop all equipment using the generator,
and idle the engine while cooling it to lower the coolant temperature.
Oil Press
Displays the pressure of the engine lubrication system. Normal pressure displayed during
operation should generally between 35 and 57 psi depending on use conditions.
However, the pressure will rise above this range immediately after starting a cold engine.
Idle the engine until it reaches the normal pressure.
Hour Meter
Oil Press
Water Temp
Fuel Meter
Speed
Selector
Switch
Содержание DGM60MK