85
Setting
(1) Setting method
(2) Number of SV setting
(3) SV setting range
(4) Key lock
MAC6A By 6 front keys (
)
MAP6A By 8 front keys (
)
MAX 8 points
Same as measuring range (within SV limiter)
OFF, 1~6 (7 levels)
Operation
Level
Contents
Key setting
OFF
No lock
1
Settings of Mode1-14 screens are not changeable.
( key operation acceptable)
2
Execution SV, manual numerical, key lock level, settings of basic
screens, step settings in program setting screens are possible.
( key operation acceptable)
3
Execution SV and a manual numerical change are possible. And change
of a key lock level is possible. ( key operation acceptable)
4
Possible to change numerical value manually and key lock level.
(
key operation acceptable)
5
Possible to change key lock level. ( key operation acceptable)
6
Possible to change key lock level. ( key operation unacceptable)
DI setting
Shift between screens prohibited. Fixed only to the basic screen.
(
key operation unacceptable)
(5) PV limiter
(6) SV limiter
(7) Unit setting
(8) PV-SV characteristics correction
(9) Input
Thermo couple
Input resistance
External resistance tolerance
Inferences of lead wire
Burn out
Compensation accuracy of reference
junction
Reference junction mode
Resistance bulb
Stipulated current
Resistance latitude of lead wire
Inferences of lead wire resistance
Voltage
Current
(10) Sampling period
(11) PV filter
(12) PV off set
(13) PV gain
(14) Characteristics correction
Within measuring range (Lo<Hi)
Over scale(HHHHH) or under scale(LLLLL) is displayed at outside measuring range
Upper limit and Lower limit can be set individually within measuring range
(Lower limit<Upper limit and within PV limit)
℃(Centigrade) (Fahrenheit) K(Kelvin)
11point ±10000dig Input
Full multi (TC, Pt, mV, V, mA)
500k
Ω
or more
100
Ω
or less
1.2
μ
V/10
Ω
Standard equipment up scale only
Within accuracy maintenance ±1℃ (Ambient temperature 5~45℃ ±2℃)
Selected between internal and external.
*1 ±0.5%FS (PV value at -100 to 0℃)
*2 ±0.7%FS (PV value at -100℃ or less)
*3 Accuracy is not guaranteed below B:400℃(752 )
About 1mA
5
Ω
or less (equivalent in the resistance value of 3 lines)
Max0.3%FS at 10
Ω
or more by each lead wire
Max0.7%FS at 20
Ω
or more by each lead wire
Input resistance : 500k
Ω
or more
Reception resistance : 100
Ω
(External resistance needed 0.05% 25ppm/℃)
50, 166.7, 250, 500ms
0~10000sec
±5000unit
±5.000%
①Linearity correction : 11point ±10000digit
②PV-PV Characteristics correction : 11point ±10000digit